NewAnalogue signal conditioning
AD-LW 110 GVC
Load monitor for cos phi and undervoltage with adjustable limits

Manufacturer image of the device family. The actual version may differ.
3-channel AC signal isolator with integrated feed-through transformers and sinusoidal outputs
Price and delivery time on request. Personal advice from Grubatec.
The AD-SW 3 GL measures three alternating currents without contact using integrated feed-through transformers and reproduces their waveforms as sinusoidal voltage signals. The outputs are galvanically isolated from the input and supply and feed downstream measurement equipment, for example in transformer monitoring.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-SW 3 GL |
| Function | 3-channel AC signal isolator with integrated feed-through transformers and sinusoidal outputs |
| Input | AC currents |
| Output | Sinusoidal voltage |
| Power supply | Wide-range power supply |
| Housing type | GL |
| Input types | AC quantities |
| Output types | AC signals |
| Supply types | Wide range, DC 20-30V, AC 230V |
| Design | DIN rail, screw terminals |
| Device functions | galvanic isolation (I/O) |
| Measuring range | Max. 0 ... 5 A AC RMS / 7.07 A amplitude - custom |
|---|---|
| Max. measurable harmonic | 100 (5 kHz) |
| Conductor diameter (external) | <6 mm (Bare conductors must not be passed through!) |
| Continuous overload | 120 % of the rated value |
| Short-term overload (1s) | Twenty times the rated value |
| Output range | 0 ... 10 V AC amplitude (7.07 V AC RMS) |
|---|---|
| Minimum load | 10 kOhm |
| Input/output phase shift | Output < 1° lagging |
| Ripple | Approx. 20 mV |
| -3 dB cut-off | Approx. 10 kHz |
|---|
| Device | <0,5 % |
|---|---|
| Temperature influence | <100 ppm / K |
| Zero error | <0,3 % |
| AC supply voltage | 50 ... 253 V AC |
|---|---|
| Rated AC voltage | 230 V AC |
| DC supply voltage | 20 ... 253 V DC |
| Rated DC voltage | 24 V DC |
| AC/DC power consumption | 3.6 VA / 1.8 W |
| Input connection technology | Feed-through transformer |
|---|---|
| Connection technology | Screw terminals |
| Construction | 35 mm DIN rail |
| Dimensions (w×h×d) | 18x75x103 mm |
| Weight | ~ 150 g |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard | EN 61326-1 |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Note | Minor signal deviations may occur during interference. |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Measurement circuit safety | EN 61010-2-030 |
| Measurement category | CAT III |
| Input / output | 3.51 kV AC + test voltage of the cable insulation (1 min) |
|---|---|
| Input / power supply | 4 kV AC (1 min) |
| Output / power supply | 3 kV AC (1 min) |
| Input / output | 300 V DC or AC RMS |
|---|---|
| Input / power supply | 300 V DC or AC RMS |
| Output / power supply | 300 V DC or AC RMS |
| Input/output | Overvoltage, overcurrent |
|---|---|
| Power supply unit | Overcurrent, overvoltage, overtemperature |
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.