Back to analogue signal processing
Product image of the device family – Grubatec – AD-SW 3 GL – AC signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-SW 3 GL

3-channel AC signal isolator with integrated feed-through transformers and sinusoidal outputs

Housing type GLDIN rail
Input
AC currents
Output
Sinusoidal voltage
Power supply
Wide-range power supply
Housing type
GL

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-SW 3 GL measures three alternating currents without contact using integrated feed-through transformers and reproduces their waveforms as sinusoidal voltage signals. The outputs are galvanically isolated from the input and supply and feed downstream measurement equipment, for example in transformer monitoring.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-SW 3 GL
Function3-channel AC signal isolator with integrated feed-through transformers and sinusoidal outputs
InputAC currents
OutputSinusoidal voltage
Power supplyWide-range power supply
Housing typeGL
Input typesAC quantities
Output typesAC signals
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsgalvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Inputs

Measuring rangeMax. 0 ... 5 A AC RMS / 7.07 A amplitude - custom
Max. measurable harmonic100 (5 kHz)
Conductor diameter (external)<6 mm (Bare conductors must not be passed through!)
Continuous overload120 % of the rated value
Short-term overload (1s)Twenty times the rated value

Outputs

Output range0 ... 10 V AC amplitude (7.07 V AC RMS)
Minimum load10 kOhm
Input/output phase shiftOutput < 1° lagging
RippleApprox. 20 mV

Cut-off frequency

-3 dB cut-offApprox. 10 kHz

Overall accuracy

Device<0,5 %
Temperature influence<100 ppm / K
Zero error<0,3 %

Power supply

AC supply voltage50 ... 253 V AC
Rated AC voltage230 V AC
DC supply voltage20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption3.6 VA / 1.8 W

Housing

Input connection technologyFeed-through transformer
Connection technologyScrew terminals
Construction35 mm DIN rail
Dimensions (w×h×d)18x75x103 mm
Weight~ 150 g

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
NoteMinor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III

Galvanic isolation, test voltages

Input / output3.51 kV AC + test voltage of the cable insulation (1 min)
Input / power supply4 kV AC (1 min)
Output / power supply3 kV AC (1 min)

Galvanic isolation, working voltages

Input / output300 V DC or AC RMS
Input / power supply300 V DC or AC RMS
Output / power supply300 V DC or AC RMS

Protective circuit

Input/outputOvervoltage, overcurrent
Power supply unitOvercurrent, overvoltage, overtemperature
Personal. Technical. Solution-focused.