Analogue signal conditioning
AD-SWT 50 SO-TRMS
50 A TRMS split-core current transformer with two-wire transmitter signal

Manufacturer image of the device family. The actual version may differ.
200 A split-core current-transformer transmitter with TRMS measurement and 4...20 mA output
Price and delivery time on request. Personal advice from Grubatec.
The AD-SWT 200 SO-TRMS converts the true RMS value of alternating currents up to 200 A into a proportional 4...20 mA current-sink signal. This two-wire version is powered through the output and is suitable for current measurement with linear and non-linear loads.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-SWT 200 SO-TRMS |
| Function | 200 A split-core current-transformer transmitter with TRMS measurement and 4...20 mA output |
| Input | AC currents |
| Output | Standard analogue signal output (current sink) |
| Power supply | Power supplied through the output (transmitter supply voltage) |
| Housing type | Not specified |
| Input types | AC quantities |
| Output types | Unipolar standard signal |
| Supply types | Transmitter |
| Design | Screw terminals |
| Device functions | galvanic isolation (I/O) |
| Measurement method | Inductive |
|---|---|
| Sampling frequency | 1 kHz (20 measurements / mains cycle) |
| Max. measurable harmonic | 10 (500 Hz) |
| Calculation method | Root-mean-square calculation (TRMS) |
| Short-term overload (1 s) | 20 times the rated value |
| Continuous overload (24 h) | 120 % of the rated value |
| Measuring range | 0 ... 50/100/200 A AC (50 Hz) |
| Max. conductor diameter | 23 mm |
| Output range | 4 ... 20 mA |
|---|---|
| Ripple | 30 µA p-p |
| DC voltage range | 10 ... 30 V DC |
|---|---|
| Rated DC voltage | 24 V DC |
| Basic accuracy | < 0.5 % (at the fundamental frequency 50 Hz) |
|---|---|
| Temperature influence | 100 ppm/K |
| Response time | < 1 s (10...90 %) |
| Dimensions (w×h×d) | 50x42x82 mm |
|---|---|
| IP rating | IP 20 |
| Connection technology | Screw terminals |
| Terminal conductor cross-section | 1.5 mm² stranded wire / 2.5 mm² solid wire |
| Terminal tightening torque | 0.5 Nm |
| Weight | ~ 200 g |
| Construction | Split-core transformer housing |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard | EN 61326-1 1) |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Measurement circuit safety | 61010-2-030 |
| Measurement category | CAT III |
| Input / output | 4 kV, 50 Hz (1 min.) + insulation of the primary conductor |
|---|
| Output | Protection against overvoltage and reverse polarity |
|---|
| Note | 1) Minor signal deviations may occur during interference. |
|---|
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.