The AD-TV 200 GS isolates, amplifies and converts standard analogue signals to suit the measurement circuit. Offset and gain can be readjusted using two front-mounted multi-turn trimmers; the integrated wide-range power supply supports different supply voltages.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 200 GS
FunctionCustom analogue signal isolator for adapting standard signals
InputStandard analogue signal input
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGS
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsStandard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Input

Current measuring range0 ...20 mA; 4 ... 20 mA1)
Input resistance50 Ohm
Voltage measuring range0 ... 10 V, 2 ... 10 V1)
Input resistance100 kOhm

Output

Current output range0 ... 20 mA; 4 ... 20 mA1)
Maximum load500 Ohm
Voltage output range0 ... 10 V; 2 ... 10 V1)
Minimum load1 kOhm
Ripple< 50 mV p-p
Note1) Adjustable; other options on request.

Housing ST

Dimensions (w×h×d)23 x 78 x 103 mm
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 120 g
Construction35 mm DIN rail

Transfer characteristics

Basic accuracy< 0.3 % of full scale
Temperature influence< 100 ppm/K of full scale

Power supply

Supply voltage20...250 V DC / 50...250 V AC
Rated voltage24 V DC / 230 V AC
Power consumptionMax 2 W / 3 VA

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 2)
EmissionsEN 55011, CISPR11 class B, group 1
Note2) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input/output3.75 kV RMS (1 min.)
Signal/power supply3 kV RMS (1 min.)

Protective circuit

Input/outputProtection against overvoltage
Power supply unitProtection against overvoltage and reverse polarity