Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 40 GVC – Multifunction signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 40 GVC

Digital multifunction signal isolator with DIP switches for standard signal selection

Housing type GVCDIN rail
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GVC
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 40 GVC isolates and amplifies standard analogue signals, with input and output ranges selected using switches or terminals. Selectable zero and full-scale trimmers allow adaptation to the measurement task; special signals can be programmed using AD-Studio.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 40 GVC
FunctionDigital multifunction signal isolator with DIP switches for standard signal selection
InputStandard analogue signal input
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGVC
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, plug-in terminals, screw terminals
Device functionsfreely configurable, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range0 ... 20 mA; 4 ... 20 mA
Resolution10 bit
Input resistance50 Ohm

Voltage input

Measuring range0 ... 10 V; 2 ... 10 V
Resolution10 bit
Input resistance> 700 kOhm

Input filter (optionally programmable via VarioConfig)

Filter10 ms/filter value (0 ... 30,000)

Current output

Output range0 ... 20 mA; 4 ... 20 mA
Resolution11 bit
Maximum load400 Ohm
Ripple<50 µA p-p

Voltage output

Output range0 ... 10 V, 2 ... 10 V
Resolution11 bit
Minimum load10 kOhm
Ripple<20 µA p-p
Linearity error<0.5 % of full scale

Accuracy

Basic accuracy0,3 %
Temperature influence<100 ppm / K
Response timeApprox. 70 ms

Trimmer function

Adjustment rangeApprox. +/-20 %

Configuration interface

NoteAD-PC -> USB
Note(via optional VarioConfig programming software)

Power supply

Supply voltage20 ... 253 V DC / 50 ... 253 V AC
Max. power consumption1.2 W/2.8 VA

Housing

Dimensions (w×h×d)18x110x128 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal tightening torque0.5 Nm
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
ConstructionDIN rail 35 mm
Weight~ 130 g

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
NoteMinor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1

Galvanic isolation, test voltages

Input/output2.5 kV RMS (1 min.)
Signal/power supply3 kV RMS (1 min.)

Protective circuit

Input/outputOvervoltage, overcurrent
Power supply unitOvercurrent, overvoltage, overtemperature
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik