Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 400 GVD – Multifunction signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 400 GVD

Digital multifunction signal isolator with standard signal and current-sink outputs

Housing type GVDDIN rail
Input
Standard analogue signal input
Output
Standard analogue signal output, current-sink output
Power supply
Wide-range power supply
Housing type
GVD
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 400 GVD isolates and amplifies current, voltage and transmitter signals and provides standard analogue signal and current-sink outputs. Ranges and outputs can be configured using AD-Studio or the optional AD-VarioControl operating module for different measurement tasks; a transmitter power supply is integrated.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 400 GVD
FunctionDigital multifunction signal isolator with standard signal and current-sink outputs
InputStandard analogue signal input
OutputStandard analogue signal output, current-sink output
Power supplyWide-range power supply
Housing typeGVD
Input typesUnipolar standard signal, bipolar standard signal, transmitter power supply
Output typesUnipolar standard signal, bipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
Interface / protocolsAD-UART
Display / operationclip-on display
DesignDIN rail, plug-in terminals, screw terminals
Device functionsSimulation, freely configurable, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range-50 ... + 50 mA DC
Input resistance40 Ohm

Voltage input

Measuring range-100 ... + 100 V DC
Input resistance1 MOhm

Transmitter power supply

No-load supply voltage24.5 V
Supply voltage at 20mA19.5 V
Current limitation~ 25 mA

Current output

Maximum output range-21.5 ... 21.5 mA DC
Maximum load400 Ohm
Ripple40 µA p-p

Voltage output

Maximum output range-10.5 ... 10.5 V DC
Minimum load10 kOhm
Ripple30 mV p-p

Current-sink output

Sink current0/4 ... 20 mA DC
Max. applied voltage35 V DC

Resolution

Input16 bit
Output12 bit

Transfer characteristics

Linearity error0.2 % of full scale
Rise time200 ms (output at 90%)
Temperature influence+/- 100 ppm/K of full scale

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption4 VA / 2.4 W

Housing

Dimensions (w×h×d)23x110x134 mm
With operating module (w×h×d)23x110x138 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 150 g
Construction35 mm DIN rail

Ambient conditions

Permissible ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standard 1)EN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
Note1) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input/output3.75 kV (1 min)
Signal/power supply4 kV (1 min)
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik