Back to analogue signal processing
Product image of the device family – Grubatec – AD-TW 25 GVD – Passive AC isolating converter

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TW 25 GVD

5 A analogue passive AC isolating converter for conversion into a galvanically isolated standard signal

Housing type GVDDIN rail
Input
AC currents
Output
Standard analogue signal output
Power supply
Not specified
Housing type
GVD
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TW 25 GVD converts 0–5 A AC current signals into a galvanically isolated 0–20 mA output signal without additional operating power. This allows current-transformer signals to be transmitted remotely or connected to suitable current inputs; operating energy is drawn directly from the measurement signal.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TW 25 GVD
Function5 A analogue passive AC isolating converter for conversion into a galvanically isolated standard signal
InputAC currents
OutputStandard analogue signal output
Power supplyNot specified
Housing typeGVD
Input typesAC quantities
Output typesUnipolar standard signal
Supply typesnone
DesignDIN rail, plug-in terminals, screw terminals
Device functionsgalvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

AD-TW 21 GVD0 ... 1 A AC (50Hz sinusoidal)
AD-TW 25 GVD0 ... 5 A AC (50Hz sinusoidal)

Current output

Maximum output range0 ... 20 mA
Maximum load400 Ohm
Load influence-0.12% / 100 Ohm

Transfer characteristics

Basic accuracy< 0.3 % of full scale
Temperature influence< 30 ppm/K
Response time< 0.5s (0 ... 90 %)

Power supply

NotePassive; no auxiliary supply required!
Power consumption from input signal~ 1.6 VA

Housing

ConstructionDIN rail (EN 50022)
IP ratingIP 20
Terminal conductor cross-sectionMax. 2.5 mm²
Weight~ 285 g

Ambient conditions

Permissible ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standard 2)EN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
Note2) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Signal/power supply2 kV (1 min)

Protective circuit

Input/outputOvervoltage, overcurrent

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik