Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-TW 41 GM provides galvanic isolation of a standard current signal with single-channel 1:1 transmission and draws its operating power directly from the input signal. The module isolates measurement circuits or protects sensitive device inputs against transferred potentials, without requiring an additional auxiliary supply.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-TW 41 GM
Function
Single-channel 1:1 isolation module for standard current signals, powered from the input
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
Not specified
Housing type
GM
Input types
Unipolar standard signal
Output types
Unipolar standard signal
Supply types
none
Design
DIN rail, screw terminals
Device functions
galvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current input
Measuring range
0 ... 20 mA
Input voltage
< 25 V
Internal voltage drop
< 2.5 V
Current output
Output range
0 ... 20 mA
Maximum load
1000 Ohm
Load error
-0.03% / 100 Ohm
Ripple
0.5 % (1000 Ohm; 20 mA)
Transfer characteristics
Basic accuracy
< 0.2 % of full scale
Input / output
1 : 1
Temperature influence
50 ppm/K of full scale
Response time
~ 20 ms
Transmission frequency
500 Hz (500 Ohm)
Housing GM
Dimensions (w×h×d)
15x42.5x102 mm
IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Weight
~ 60 g
Construction
35 mm DIN rail
Housing ST
Dimensions (w×h×d)
15x42.5x102 mm
IP rating
IP 20
Note
Pluggable
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Weight
~ 50 g
Construction
35 mm DIN rail
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Galvanic isolation
Note
Basic insulation, functional isolation
Working voltage
50 VDC
Input/output test voltage
500 V, 50 Hz (1 min.)
Protective circuits
Inputs
Protection against overvoltage
Output
Protection against overvoltage
Note
1) Minor signal deviations may occur during interference.
Other versions.
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.