Back to pulse & frequency
Product image of the device family – Grubatec – AD-KI 100 GS-O – Contact protection and pulse shaping

Manufacturer image of the device family. The actual version may differ.

Pulses & frequency

AD-KI 100 GS-O

Pulse shaper for protecting low-power sensor contacts, with galvanically isolated solid-state outputs

Housing type GSDIN rail
Input
Frequency or pulse input
Output
Solid-state output
Power supply
Wide-range power supply
Housing type
GS
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-KI 100 GS-O conditions binary sensor signals and outputs pulses with a duration adjustable on the front panel. Its galvanically isolated solid-state outputs operate without wear and are suitable for transmitting counting pulses or switching signals from low-power contacts.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-KI 100 GS-O
FunctionPulse shaper for protecting low-power sensor contacts, with galvanically isolated solid-state outputs
InputFrequency or pulse input
OutputSolid-state output
Power supplyWide-range power supply
Housing typeGS
Input typesPulses, NAMUR signals, optical sensors
Output typesSolid-state switch, S0, pulses
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsgalvanic isolation (I/O), quantity pulses, energy pulses
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Pulse input

Min. pulse width2 ms
NAMUR supply voltageApprox. 8.2 V DC
Logic levels for NAMUR signalsLow < 1.2 mA ... High > 2.1 mA
Max. input voltage (active)30 V DC
Logic levels for active signalsLow < 5 V ... High > 20 V
Contact typeVolt-free

Pulse processing

Adjustable output pulse duration0.2 ... 10 s (0.5 s factory setting)

Relay outputs

Maximum AC switching load250 V, 2 A
Maximum DC switching load50 V, 2 A
Contact configurationVolt-free changeover contact
Mechanical switching cycles10000000
At 230V/2A AC, cos(phi)=1600000
At 230V/2A AC, cos(phi)=0.4200000
At 24V/1 A DC200000

Solid-state outputs

Max. switching voltage30 V DC
Max. switching current50 mA DC
Working voltage at pull-up10 ... 30 V DC
Internal pull-up5 kOhm

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption3 VA / 2W

Transfer characteristics

Temperature influence100 ppm/K
Response time~ 5 ms

Housing

Dimensions (w×h×d)23x81x103 mm
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 115 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input / output3.75 kV, 50 Hz (1 min.)
Signal / power supply4 kV, 50 Hz (1 min.)

Protective circuits

InputsProtection against overvoltage
Power supply unitProtection against overvoltage, overtemperature and reverse polarity

Note1) Minor signal deviations may occur during interference.

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik