Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-LU 320 GVD measures electrical quantities in a single-phase AC network and outputs selected measured values through two freely scalable analogue outputs. For energy accounting in systems and machines, it can be adapted to the measurement task using AD-Studio or the VarioControl interface with an optional operating module.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 320 GVD
Function
Single-phase power transducer with integrated current transformer and analogue outputs
Input
1x AC voltage and 1x AC current
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GVD
Input types
AC quantities
Output types
Unipolar standard signal
Supply types
Wide range, DC 20-30V, AC 230V
Interface / protocols
AD-UART
Display / operation
clip-on display
Design
DIN rail, plug-in terminals, screw terminals
Device functions
freely configurable, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current input
Measuring ranges
0 ... 1 A AC; 0 ... 5 A AC
Max. measurable harmonic
40
Voltage input
Measuring range
10 ... 253 V AC
Input resistance
> 1 MOhm
Current output
Output range
0/4 ... 20 mA
Max. load
400 Ohm
Resolution
11 bit
Ripple
25 µA p-p
Voltage output
Output range
0/2 ... 10 V
Min. load
10 kOhm
Resolution
11 bit
Ripple
20 mV p-p
Power supply
AC voltage range
50 ... 253 V AC, 50/60 Hz
Rated AC/DC voltage
230 V AC / 24 V DC
DC voltage range
20 ... 253 V DC
AC/DC power consumption
3.4 VA / 1.8 W
AC/DC power consumption with operating module
3.6 VA / 2.0 W
Transfer characteristics
Basic accuracy
< 0.5 % (class 0.5)
Temperature influence
80 ppm/K
Response time
< 0.5 s (0...90 %, 100...10 %)
Housing
Dimensions (w×h×d)
23x110x134mm
With operating module (w×h×d)
23x110x138 mm
IP rating
IP 20
Connection technology
Removable screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Terminal stripping length
6 mm
Weight
~ 150 g
Construction
35 mm DIN rail
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Note
1) Minor signal deviations may occur during interference.
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
EN 61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Input to analogue outputs / power supply
4 kV, 50 Hz (1 min.)
Power supply to analogue outputs
3 kV, 50 Hz (1 min.)
Protective circuits
Inputs
Protection against overvoltage
Power supply unit
Protection against overtemperature, overvoltage and overcurrent