Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-LU 410 GT measures active power in three-phase networks and outputs it as a standard analogue signal for further processing. Rated voltage, power range and output signal are adapted to the installation; the analogue design also allows brief load changes to be detected.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 410 GT
Function
Three-phase analogue power transducer for active-power measurement with standard signal output
Input
3x AC voltage and 3x AC current
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GT
Input types
Power/energy, AC quantities
Output types
Unipolar standard signal, bipolar standard signal
Supply types
Wide range, DC 20-30V, AC 230V
Design
DIN rail, screw terminals
Device functions
galvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Voltage inputs
Rated frequency
50/60 Hz
Rated star/delta voltage
230/400 V AC
Max. star/delta voltage
300/520 V AC
Current consumption per phase
0.5 mA AC
Continuous overload capacity
120% of the rated voltage
Surge overload capacity
600 V AC, 1s
Current inputs
Rated current range I1, I2, I3
0 ... 1 A AC, 0 ... 5 A AC
Surge overload capacity
100 A AC, 1s
Continuous load capacity
6 A AC
Continuous overload capacity
120% of the rated current
Input resistance per phase
~20 mOhm
Output
Type
Current (mA) or voltage (V); specify when ordering
Current output
Maximum load
400 Ohm @ 20 mA
Maximum output range
-21 ... 21 mA @ 50 Ohm
Voltage output
Minimum load
10 kOhm @ 10 V
Maximum output range
-12 ... 12 V (10kOhm)
Accuracy
Accuracy class
0.5% under reference conditions
Temperature drift cos(phi)=1
~3 µA/K @ -10...70°C
Frequency influence
~3.5 µA/Hz @ 40 ... 60Hz
Response time
100 ms (10 ... 90)%
Power supply
DC
1.6 W @ 20 ... 253 V DC
AC
3.9 VA @ 50 ... 253 V AC
Housing
Housing IP rating
IP20
Connection technology
Screw terminals
Fine-stranded conductor cross-section
2.5 mm2
Solid conductor cross-section
4 mm2
Max. terminal torque
0.8 Nm
Installation
DIN rail
Weight
~ 450 g
Ambient conditions
Operating temperature
-25 ... 70 °C
Storage, transport
-40 ... 70 °C
Electromagnetic compatibility
Product family standard
EN 61326-1
Emission
EN 55011, CISPR11 class B, group 1
Immunity
DIN EN 61000-6-5
Note
Minor signal deviations may occur during interference.