Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-LU 45S GT-PN uses external split-core current transformers for three-phase measurement and transfers measurement data via PROFINET; an RS485 interface is also provided. This version with separate supply terminals has a 2-port switch that allows the PROFINET connection to continue directly to the next device.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 45S GT-PN
Function
Three-phase power transducer with PROFINET and separate supply terminals
Input
3x AC voltage and 3x AC current
Output
Not specified
Power supply
Power supplied from the measured voltage
Housing type
GT
Input types
Power/energy, AC quantities
Supply types
Wide range, DC 20-30V, AC 230V
Interface / protocols
RS485 bus, PROFINET, Modbus-RTU
Display / operation
remote display (bus)
Design
DIN rail, screw terminals
Device functions
freely configurable, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current inputs (I1...I3)
Measuring ranges
0 ... 33.3 mA (via split-core current transformers)
Input resistance
Approx. 10 Ohm
Max. measurable harmonic
40
Voltage inputs (L1...L3)
Measuring range
80 ... 253 V AC (AD-LU 40 GT) 0 ... 253 V AC (AD-LU 40S GT)
Input resistance
Approx. 970 kOhm
PROFINET
Ethernet
2 Port Switch
Protocol specification
PROFINET IO
Default IP address
0.0.0.0
PROFIBUS
Address setting
BCD switch 00...99
Bus termination
120 Ohm at both ends
Max. bus length
500 m (no spur lines)
Conductor
Twisted and screened
RS485 bus
Software protocol
Modbus-RTU
Data format
19200, e, 8, 1
Max. bus nodes
99
Bus termination
120 Ohm at both ends
Bus termination
120 Ohm at both ends
Max. bus length
500 m (no spur lines)
Conductor
Twisted and screened
Address setting
BCD switch 00...99
Power supply
AC voltage range
80 ... 253 V AC, 50/60 Hz (see voltage input)
Rated AC voltage
230 V AC
Power consumption
Max. 4 VA
Power supply (-S)
AC voltage range
50 ... 253 V AC, 50/60 Hz
DC voltage range
20 ... 253 V DC
Rated AC/DC voltage
230 V AC / 24 V DC
AC/DC power consumption
Max. 4 VA / 3 W
Measurement
Basic accuracy
<= 0.5 % (class 0.5)
Temperature influence
80 ppm/K
Sampling interval
200 ms
Housing
Dimensions (w×h×d)
105x90x71 mm
IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.6 Nm
Weight
~ 210 g
Construction
35 mm DIN rail
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class A, group 1
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
EN 61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Mains side to fieldbus
4 kV, 50 Hz (1 min.)
Mains side to controls
4 kV, 50 Hz (1 min.)
Note
1) Minor signal deviations may occur during interference.
Other versions.
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.