Power & energy

AD-LU 610 GT-O

Three-phase power transducer with analogue and solid-state outputs and RS485

Housing type GTRS485 bus
Input
3x AC voltage and 3x AC current
Output
Standard analogue signal output and solid-state output
Power supply
Power supplied from the measured voltage
Housing type
GT
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-LU 610 GT-O measures electrical quantities in three-phase networks using integrated feed-through current transformers and provides them at analogue outputs. This version with a solid-state output supports higher-frequency energy pulses; RS485 allows measured values to be read and device settings to be configured using AD-Studio.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-LU 610 GT-O
FunctionThree-phase power transducer with analogue and solid-state outputs and RS485
Input3x AC voltage and 3x AC current
OutputStandard analogue signal output and solid-state output
Power supplyPower supplied from the measured voltage
Housing typeGT
Input typesPower/energy, AC quantities
Output typesUnipolar standard signal, solid-state switch, S0, pulses
Supply typesWide range, AC 230V
Interface / protocolsRS485 bus, Modbus-RTU
Display / operationremote display (bus)
DesignDIN rail, screw terminals
Device functionsfreely configurable, limit monitoring, energy pulses, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current inputs (I1...I3)

Measuring ranges0 ... 1 A AC; 0 ... 5 A AC;0 ... 20 A AC
Max. conductor diameter4.8 mm
Max. measurable harmonic40

Voltage inputs (L1...L3)

Measuring range80 ... 253 V AC
Input resistance> 900 kOhm

Current output

Output range0/4 ... 20 mA
Max. load400 Ohm
Resolution11 bit
Ripple25 µA p-p

Voltage output

Output range0/2 ... 10 V
Min. load10 kOhm
Resolution11 bit
Ripple30 mV p-p

Relay output

Maximum AC switching load250 V, 2 A
Maximum DC switching load50 V, 2 A
Contact configurationVolt-free changeover contact
Mechanical switching cycles10000000
At 230V/2A AC, cos(phi)=1600000
At 230V/2A AC, cos(phi)=0.4200000
At 24V/2A DC200000
Pulse duration min ... max500 ms ... 10000 ms

Alternatively: transistor output

Maximum DC switching load30 V, 50 mA
Pulse duration min ... max50 ms ... 10000 ms

Power supply

AC voltage range80 ... 253 V AC, 50/60 Hz (see voltage input)
Rated AC voltage230 V AC
Power consumptionMax. 4.7 VA

RS485 bus

Software protocolModbus-RTU
Data format19200, e, 8, 1
Address switch0...9 (0: service position)
Bus termination120 Ohm at both ends
Max. bus length500 m (no spur lines)
ConductorTwisted and screened

Transfer characteristics - relative to full scale

Basic accuracy< 0.5 % (class 0.5)
Temperature influence80 ppm/K
Response time< 0.5 s

Housing

Dimensions (w×h×d)71x90x70 mm
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.6 Nm
Terminal stripping length6 mm
Weight~ 170 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III

Galvanic isolation, test voltages

Mains side to analogue outputs4 kV, 50 Hz (1 min.)
Mains side to relay contact4 kV, 50 Hz (1 min.)
Relay contact to analogue outputs4 kV, 50 Hz (1 min.)

Protective circuits

InputsProtection against overvoltage
Power supply unitProtection against overtemperature, overvoltage and overcurrent
Analogue outputsProtection against overvoltage

Note1) Minor signal deviations may occur during interference.

Other versions.