Model overview.
The AD-LU 620 GVF measures electrical quantities in three-phase networks using integrated current transformers and outputs selected values as standard analogue signals. Relay and solid-state outputs also provide limit alarms or pulse outputs for energy accounting; configuration is possible with AD-Studio or the optional AD-VarioControl.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 620 GVF
Function
Three-phase digital power transducer with integrated current transformers and analogue, relay and solid-state outputs
Input
3x AC voltage and 3x AC current
Output
Standard analogue signal output, relay and solid-state outputs
Power supply
Wide-range power supply
Housing type
GVF
Input types
Power/energy, AC quantities
Output types
Unipolar standard signal, relay, solid-state switch, S0, pulses
Supply types
Wide range, DC 20-30V, AC 230V
Interface / protocols
AD-UART
Display / operation
clip-on display
Design
DIN rail, plug-in terminals, screw terminals
Device functions
Simulation, freely configurable, limit monitoring, energy pulses, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current inputs (I1...I3)
Measuring ranges
0 ... 1 A AC; 0 ... 5 A AC
Max. measurable harmonic
40
Voltage inputs (L1...L3)
Measuring range
10 ... 253 V AC
Input resistance
> 1 MOhm
Current output
Output range
0/4 ... 20 mA
Max. load
400 Ohm
Resolution
11 bit
Ripple
25 µA p-p
Voltage output
Output range
0/2 ... 10 V
Min. load
10 kOhm
Resolution
11 bit
Ripple
20 mV p-p
Solid-state output
Maximum DC switching load
30 V, 50 mA
Pulse duration min ... max
50 ms ... 10000 ms
Relay output
Maximum AC switching load
250 V, 2 A
Maximum DC switching load
50 V, 2 A
Contact configuration
Volt-free changeover contact
Mechanical switching cycles
1 * 107
At 230V/2A AC, cos(phi)=1
6 * 105
At 230V/2A AC, cos(phi)=0.4
2 * 105
At 24V/2A DC
2 * 105
Pulse duration min ... max
500 ms ... 10000 ms
Power supply
AC voltage range
50 ... 253 V AC, 50/60 Hz
Rated AC/DC voltage
230 V AC / 24 V DC
DC voltage range
20 ... 253 V DC
AC/DC power consumption
4.6 VA / 2.4 W
AC/DC power consumption with operating module
4.8 VA / 2.6 W
Transfer characteristics
Basic accuracy
< 0.5 % (class 0.5)
Temperature influence
80 ppm/K
Response time
< 0.5 s
Housing
Dimensions (w×h×d)
33x110x134mm
With operating module (w×h×d)
33x110x138 mm
IP rating
IP 20
Connection technology
Removable screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Terminal stripping length
6 mm
Weight
~ 190 g
Construction
35 mm DIN rail
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Note
1) Minor signal deviations may occur during interference.
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
EN 61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Input to outputs / power supply
4 kV, 50 Hz (1 min.)
Power supply to outputs
3 kV, 50 Hz (1 min.)
Relay contacts to analogue outputs
3 kV, 50 Hz (1 min.)
Protective circuits
Inputs
Protection against overvoltage
Power supply unit
Protection against overtemperature, overvoltage and overcurrent