Back to power & energy
Product image of the device family – Grubatec – AD-LU 625 GVF – Power transducer

Manufacturer image of the device family. The actual version may differ.

Power & energy

AD-LU 625 GVF

Three-phase power transducer for split-core current transformers, with analogue, relay and solid-state outputs

Housing type GVFDIN rail
Input
3x AC voltage and 3x AC current
Output
Standard analogue signal output, relay and solid-state outputs
Power supply
Wide-range power supply
Housing type
GVF
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-LU 625 GVF measures three-phase electrical quantities using external split-core current transformers and provides measured values, limit alarms or energy pulses at its outputs. AD-Studio and the optional AD-VarioControl operating module allow measuring ranges and outputs to be adjusted.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-LU 625 GVF
FunctionThree-phase power transducer for split-core current transformers, with analogue, relay and solid-state outputs
Input3x AC voltage and 3x AC current
OutputStandard analogue signal output, relay and solid-state outputs
Power supplyWide-range power supply
Housing typeGVF
Input typesPower/energy, AC quantities
Output typesUnipolar standard signal, relay, solid-state switch, S0, pulses
Supply typesWide range, DC 20-30V, AC 230V
Interface / protocolsAD-UART
Display / operationclip-on display
DesignDIN rail, plug-in terminals, screw terminals
Device functionsSimulation, freely configurable, limit monitoring, energy pulses, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current inputs (I1...I3)

Measuring ranges0 ... 0.05 A AC from a split-core current transformer
Max. measurable harmonic40

Voltage inputs (L1...L3)

Measuring range10 ... 253 V AC
Input resistance> 1 MOhm

Current output

Output range0/4 ... 20 mA
Max. load400 Ohm
Resolution11 bit
Ripple25 µA p-p

Voltage output

Output range0/2 ... 10 V
Min. load10 kOhm
Resolution11 bit
Ripple20 mV p-p

Solid-state output

Maximum DC switching load30 V, 50 mA
Pulse duration min ... max50 ms ... 10000 ms

Relay output

Maximum AC switching load250 V, 2 A
Maximum DC switching load50 V, 2 A
Contact configurationVolt-free changeover contact
Mechanical switching cycles1 * 107
At 230V/2A AC, cos(phi)=16 * 105
At 230V/2A AC, cos(phi)=0.42 * 105
At 24V/2A DC2 * 105
Pulse duration min ... max500 ms ... 10000 ms

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC/DC voltage230 V AC / 24 V DC
DC voltage range20 ... 253 V DC
AC/DC power consumption4.6 VA / 2.4 W
AC/DC power consumption with operating module4.8 VA / 2.6 W

Transfer characteristics

Basic accuracy< 0.5 % (class 0.5)
Temperature influence80 ppm/K
Response time< 0.5 s

Housing

Dimensions (w×h×d)33x110x134mm
With operating module (w×h×d)33x110x138 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Terminal stripping length6 mm
Weight~ 180 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1
Note1) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III

Galvanic isolation, test voltages

Input to outputs / power supply4 kV, 50 Hz (1 min.)
Power supply to outputs3 kV, 50 Hz (1 min.)
Relay contacts to analogue outputs3 kV, 50 Hz (1 min.)

Protective circuits

InputsProtection against overvoltage
Power supply unitProtection against overtemperature, overvoltage and overcurrent
Analogue outputsProtection against overvoltage
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80