The AD-LU 650 GA measures three-phase quantities using integrated current transformers and provides four standard analogue signal outputs, two relay outputs and RS485. Different measured quantities can be assigned to the analogue outputs, while the switching outputs can have their own monitoring functions, such as limit alarms or energy pulses.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 650 GA
Function
Three-phase power transducer with integrated current transformers, four analogue outputs and two relays
Input
3x AC voltage and 3x AC current
Output
4x standard analogue signal output and 2x relay
Power supply
Power supplied from the measured voltage
Housing type
GA
Input types
Power/energy, AC quantities
Output types
Unipolar standard signal, relay, S0, pulses
Supply types
Wide range, DC 20-30V, AC 230V
Interface / protocols
RS485 bus, Modbus-RTU
Display / operation
remote display (bus)
Design
DIN rail, screw terminals
Device functions
freely configurable, limit monitoring, energy pulses, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Voltage inputs
U1N, U2N, U3N rated
230 V AC
U1N, U2N, U3N Max
300 V AC
Current consumption per phase
0.5 mA AC
Surge overload capacity
600 V AC, 1s
Current inputs
Rated current range I1, I2, I3
0 ... 1 A AC, 0 ... 5 A AC
Surge overload capacity
100 A AC, 1s
Continuous load capacity
6 A AC
Input resistance per phase
~20 mOhm
Analogue outputs
Number
4
Note
Current or voltage configurable
Current outputs
Maximum ripple
40 µA p-p
Maximum load
400 Ohm
Maximum output range
-21 ... 21 mA
Voltage outputs
Maximum ripple
20 mV p-p
Minimum load
10 kOhm
Maximum output range
-10.5 ... 10.5 V
Contact outputs
Normally open contact
2
AC switching capacity
250 V AC, 2A, 50Hz
DC switching capacity
50 V DC, 2A
Optocoupler outputs
DC switching capacity
30 V DC, 50 mA DC
Accuracy
Accuracy class
0,5%
Temperature influence
< 200 ppm/K
Frequency influence
~0.2 %, 40 ... 60 Hz
Phase-angle influence
~0.2 %, 40 ... 60 Hz
Response time
~500 ms, 10 ... 90 %
Communication interface
Physical
RS-485
Parameters
19200, 8, 1 , even
Protocol
Modbus RTU
Power supply
DC
20 ... 253 V DC, 5 W
AC
50 ... 253 V AC, 9 VA
Housing
IP rating
IP 20
Connection technology
Screw terminals
Fine-stranded conductor cross-section
2.5 mm2
Solid conductor cross-section
4 mm2
Installation
DIN rail
Weight
~ 450 g
Ambient conditions
Operating temperature
-10 ... 50 °C
Storage, transport
-25 ... 80 °C
Electromagnetic compatibility
Product family standard
EN 61326-1
Emission
EN 55011, CISPR11 class B, group 1
Note
Minor signal deviations may occur during interference.