Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-LU 70 FE-PB measures electrical quantities in three-phase networks using integrated current transformers and shows them on a TFT display. In panel-mounted installations, the measurement data is also available via PROFIBUS, for example for consumption monitoring or integration into an energy management system.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 70 FE-PB
Function
Panel-mount three-phase power transducer with TFT display and PROFIBUS
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current inputs
Measuring ranges
0 ... 1/5/20 A AC
Maximum conductor diameter
4.8 mm²
Voltage inputs/power supply
Rated voltage
230 V AC
Rated frequency
50 Hz
Frequency range
40 ... 100 Hz
Measuring range
80 ... 253 V AC
Max. power consumption L1
4 VA
Input resistance L2, L3
970 kOhm
Optocoupler outputs
Maximum switching voltage
30 V DC
Maximum switching current
50 mA DC
PROFINET
Ethernet
2 Port Switch
Protocol specification
PROFINET IO
Default IP address
0.0.0.0
PROFIBUS
Bus termination
120 Ohm at both ends
Max. bus length
500 m (no spur lines)
Conductor
Twisted and screened
Display
Type
TFT
Resolution
320x240 pixels
Accuracy
Class
0,5
Temperature influence
100 ppm/K
Housing
Dimensions (w×h×d)
96x96x123 mm
Panel cut-out (w×h)
92x92 mm
Front/housing IP rating
IP54/IP20
Connection technology
Pluggable screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Weight
~ 250 g
Construction
Panel mounting
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class A, group 1
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
EN 61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Mains - PROFINET/PROFIBUS
4 kV, 50 Hz (1 min.)
Mains - digital outputs
4 kV, 50 Hz (1 min.)
Note
1) Minor signal deviations may occur during interference.
Other versions.