Analogue signal conditioning

AD-SMK 330 GS

Analogue limit switch with transmitter power supply and thumbwheel coding switches

Housing type GSDIN rail
Input
Standard analogue signal input
Output
Relay
Power supply
Wide-range power supply
Housing type
GS
Marked by the manufacturer as no longer available.
Ask us about a suitable replacement solution.
Datasheet (EN)

Advice on a successor model from Grubatec.

Model overview.

The AD-SMK 330 GS monitors analogue current or voltage signals and switches two volt-free changeover contacts according to the set limits. The integrated supply powers 2-wire and 3-wire transmitters; front-mounted thumbwheel coding switches allow limits to be set for quantities such as flow, level or temperature.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-SMK 330 GS
FunctionAnalogue limit switch with transmitter power supply and thumbwheel coding switches
InputStandard analogue signal input
OutputRelay
Power supplyWide-range power supply
Housing typeGS
Input typesUnipolar standard signal, transmitter power supply
Output typesRelay
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsLimit monitoring
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current inputs

Measuring range4 ... 20 mA
Input resistance50 Ohm

Voltage input

Measuring range0 ... 10 V
Input resistance400 kOhm

Transmitter power supply

No-load/full-load voltageLess than 21 V / greater than 18 V
Current limitationApprox. 30 mA

Relay outputs A/B

ContactsVolt-free changeover contacts
Max. AC switching capacity250 V AC, 2 A AC, 50Hz
Max. DC switching capacity50 V DC, 2 A DC
NoteSwitching cycles
Mechanical107
AC: 230V / 2A, cos(phi)=16 * 105
AC: 230V / 2A, cos(phi)=0.42 * 105
DC: 24V / 1A2 * 105

Transfer characteristics

Basic accuracy1 % (1 digit)
Temperature influence+/- 100 ppm/K of full scale
Response time100 ms

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption2.4 VA / 1.8 W

Housing

ConstructionDIN rail (EN 50022)
IP ratingIP 20
Terminal conductor cross-sectionMax. 2.5 mm²
Weight~ 200 g

Ambient conditions

Permissible ambient temperature-10 ... 50 °C
Storage and transport-10 ... 60 °C (avoid condensation)

EMC

Product family standard 1)EN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
Note1) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input/relay4 kV (1 min)
Input/power supply3 kV (1 min)
Relay/power supply4 kV (1 min)
Between relays3 kV (1 min)

Protective circuit

InputOvervoltage
Power supply unitOvercurrent, overvoltage, overtemperature