Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-SWT 200 SO converts sinusoidal alternating currents up to 200 A into a proportional 4...20 mA signal and is powered through the output. Its split-core format allows use in existing installations, for example to measure pump, motor or generator currents.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-SWT 200 SO
Function
Split-core current-transformer transmitter for sinusoidal AC currents up to 200 A, with 4...20 mA signal
Input
AC currents
Output
Standard analogue signal output (current sink)
Power supply
Power supplied through the output (transmitter supply voltage)
Housing type
Not specified
Input types
AC quantities
Output types
Unipolar standard signal
Supply types
Transmitter
Design
Screw terminals
Device functions
galvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Primary current
Measurement method
Inductive
Measuring range
0 ... 50/100/200 A AC
Max. conductor diameter
23 mm
Transmitter output
Output range
4 ... 20 mA
Ripple
50 µA p-p
Transmitter power supply
DC voltage range
10 ... 30 V DC
Rated DC voltage
24 V DC
Transfer characteristics
Basic accuracy
< 1 %
Temperature influence
100 ppm/K
Response time
< 2 s (10...90 %)
Housing
Dimensions (w×h×d)
50x42x82 mm
IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
1.5 mm² stranded wire / 2.5 mm² solid wire
Terminal tightening torque
0.5 Nm
Weight
~ 200 g
Construction
Split-core transformer housing
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Input / output
4 kV, 50 Hz (1 min.)
Protective circuits
Output
Protection against overvoltage and reverse polarity
Note
1) Minor signal deviations may occur during interference.
Other versions.
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.