NewAnalogue signal conditioning
AD-LW 110 GVC
Load monitor for cos phi and undervoltage with adjustable limits

Manufacturer image of the device family. The actual version may differ.
Analogue signal splitter/isolator with two outputs in a 6.2 mm design
Price and delivery time on request. Personal advice from Grubatec.
The AD-TV 12 GX duplicates an analogue measurement signal onto two synchronised current outputs, galvanically isolated from one another and from the input and supply. For separate processing of a signal, current or voltage input and standard signal combinations can be selected using DIP switches.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-TV 12 GX |
| Function | Analogue signal splitter/isolator with two outputs in a 6.2 mm design |
| Input | Standard analogue signal input |
| Output | 2x standard analogue signal output |
| Power supply | 24V DC |
| Housing type | GX |
| Input types | Unipolar standard signal |
| Output types | Unipolar standard signal |
| Supply types | DC 20-30V |
| Design | DIN rail, screw terminals, 6.3 mm width |
| Device functions | Standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation |
| Current input range | 0 ... 20 mA; 4 ... 20 mA |
|---|---|
| Voltage input range | 0 ... 10 V |
| Current input resistance | 50 Ohm |
| Voltage input resistance | 100 kOhm |
| 2 current outputs | 0 ... 20 mA; 4 ... 20 mA |
|---|---|
| Maximum load | 400 Ohm per channel |
| Maximum ripple | 50 mV p-p |
| Signal clamping | 20 mA |
| Voltage range | 18 ... 30 V DC |
|---|---|
| Rated voltage | 24 V DC |
| Power consumption | < 1.5 W |
| Overall accuracy | < 0.2 % of full scale |
|---|---|
| Linearity error | < 0.2 % of full scale |
| Temperature influence | 70 ppm/K of full scale |
| Response time | ~ 10 ms |
| Dimensions (W×H×D) | 6.2 x 92 x 101 mm³ |
|---|---|
| IP rating | IP 20 |
| Connection technology | Screw terminals (2.5 mm² stranded wire / 4 mm² solid wire) |
| Terminal tightening torque | 0.5 Nm |
| Weight | ~ 70 g |
| Construction | 35 mm DIN rail |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... +70 °C (avoid condensation) |
| Product family standard 1) | EN 61326-1 |
|---|---|
| Emissions 2) | EN 55011, CISPR11 class A, group 1 |
| Note | 1) Minor signal deviations may occur during interference. |
| Note | 2) Warning: This equipment is not intended for use in residential environments and may not provide adequate protection for radio reception in such environments. |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Input / output | 1.5 kV (1 min.) |
|---|---|
| Signal / power supply | 1.5 kV (1 min.) |
| Inputs | Protection against overvoltage |
|---|---|
| Outputs | Protection against overvoltage |
| Power supply unit | Protection against overvoltage and reverse polarity |
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.