NewAnalogue signal conditioning
AD-LW 110 GVC
Load monitor for cos phi and undervoltage with adjustable limits

Manufacturer image of the device family. The actual version may differ.
Custom analogue signal isolator as a Eurocard plug-in board
Price and delivery time on request. Personal advice from Grubatec.
The AD-TV 200 EV isolates, amplifies or converts analogue measurement signals on a custom Eurocard plug-in board. Depending on the version, up to four mutually isolated channels are possible; their input and output signal types can be freely selected and adjusted using front-mounted multi-turn trimmers.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-TV 200 EV |
| Function | Custom analogue signal isolator as a Eurocard plug-in board |
| Input | Standard analogue signal input in Eurocard format |
| Output | Standard analogue signal output |
| Power supply | 24V DC or 230V AC |
| Housing type | EV |
| Input types | Unipolar standard signal |
| Output types | Unipolar standard signal |
| Supply types | DC 20-30V, AC 230V |
| Design | Eurocard |
| Device functions | Standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation |
| Current measuring range | 0 ...20 mA; 4 ... 20 mA1) |
|---|---|
| Input resistances | 50 Ohm |
| Voltage measuring range | 0 ... 10 V, 2 ... 10 V1) |
| Input resistances | 100 kOhm |
| Current output range | 0 ... 20 mA; 4 ... 20 mA1) |
|---|---|
| Maximum load | 500 Ohm |
| Voltage output range | 0 ... 10 V; 2 ... 10 V1) |
| Minimum load | 500 Ohm |
| Ripple | < 50 mV p-p |
| Note | 1) Selectable and adjustable per channel; other options on request. |
| Basic accuracy | < 0,3 % |
|---|---|
| Temperature influence | < 100 ppm/K |
| Supply voltage | 20 ... 253 V DC / 50 ... 253 V AC |
|---|---|
| Rated voltage | 24 V DC / 230 V AC |
| Power consumption | 5.4 W / 11 VA |
| Construction | 19"-Eurocard 4TE |
|---|---|
| IP rating | IP 00 |
| Weight | ~ 160 g |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard | EN 61326-1 2) |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Note | 2) Minor signal deviations may occur during interference. |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Input/output | 0.5 kV RMS (1 min.) |
|---|---|
| Channel/channel | 0.5 kV RMS (1 min.) |
| Signal/power supply | 3 kV RMS (1 min.) |
| Input/output | Protection against overvoltage |
|---|---|
| Power supply unit | Protection against overvoltage and reverse polarity |
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.