Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 3 GX – Multifunction signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 3 GX

Analogue multifunction signal isolator in a 6.2 mm design with DIP switches

Housing type GXDIN rail
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
24V DC
Housing type
GX
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 3 GX isolates, converts and amplifies DC current or voltage signals in a 6.2 mm wide housing. Signals are selected using DIP switches; after changing the measuring range, zero and full scale must be readjusted with the trimmers to match the device to the selected range.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 3 GX
FunctionAnalogue multifunction signal isolator in a 6.2 mm design with DIP switches
InputStandard analogue signal input
OutputStandard analogue signal output
Power supply24V DC
Housing typeGX
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesDC 20-30V
DesignDIN rail, screw terminals, 6.3 mm width
Device functionsStandard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range0 ... 20 mA; 4 ... 20 mA
Input resistance50 Ohm

Voltage input

Measuring range0 ... 5 V; 0 ... 10 V
Input resistance10 kOhm / V

Current output

Output range0 ... 20 mA
Maximum load500 Ohm
Open-circuit voltage< 13 V

Voltage output

Output range0 ... 10 V
Minimum load500 Ohm
Current limitation< 28 mA

Transfer characteristics

Response time< 50 ms (10-90 %)
Linearity error< 0.1 % of full scale
Ripple< 0.1 % of full scale
Temperature influence< 70 ppm/K of full scale
Zero trimmer+/- 22% of full scale
Full-scale trimmer+/- 5% of full scale

Power supply

Voltage range18 ... 30 V DC
Rated voltage24 V DC
Power consumption< 850 mW

Housing

Dimensions (W×H×D)6.2 x 92 x 101 mm³
ConstructionDIN rail EN 50022
IP ratingIP 20
Connection technologyScrew terminals (2.5 mm² stranded wire / 4 mm² solid wire)
Terminal tightening torque0.5 Nm
Weight~ 70 g

Ambient conditions

Ambient temperature-10 ... +50 °C
Storage and transport-10 ... +70 °C (avoid condensation)

EMC

Product family standardEN 61326-1
NoteMinor signal deviations may occur during interference.
EmissionsEN 55011, CISPR11 class A, group 1
NoteWarning: This equipment is not intended for use in residential environments and may not provide adequate protection for radio reception in such environments.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input/output1.5 kV, 1 min
Signal/power supply1.5 kV, 1 min