Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 30 GL – Multifunction signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 30 GL

Analogue multifunction signal isolator with signal selection via terminals and trimmers

Housing type GLDIN rail
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GL
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 30 GL isolates, converts and amplifies DC current or voltage signals and provides a linear analogue output signal. Signals are configured using terminals and front-panel trimmers to suit the measurement task; input, output and supply are galvanically isolated from one another.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 30 GL
FunctionAnalogue multifunction signal isolator with signal selection via terminals and trimmers
InputStandard analogue signal input
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGL
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsStandard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range0/4 ... 20 mA
Input resistance85 Ohm

Voltage input

Measuring range0/2 ... 10 V
Input resistance> 100 kOhm

Current output

Output range0/4 ... 20 mA
Maximum load500 Ohm
Ripple50 µA p-p

Voltage output

Output range0/2 ... 10 V
Minimum load> 10 kOhm
Ripple50 mV p-p

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption2.3 VA / 1W

Transfer characteristics

Basic accuracy< 0.2 % of full scale
Temperature influence100 ppm/K of full scale
Response time~ 20 ms

Housing

Dimensions (w×h×d)18x78x103 mm
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 100 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input / output3.75 kV, 50 Hz (1 min.)
Signal / power supply4 kV, 50 Hz (1 min.)

Protective circuits

InputsProtection against overvoltage
OutputProtection against overvoltage
Power supply unitProtection against overvoltage and reverse polarity

Note1) Minor signal deviations may occur during interference.
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik