Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-TV 32 GL isolates, converts and amplifies analogue current or voltage signals configured through terminals and trimmers. For manual operation, a potentiometer can set the output setpoint; during this simulation, the input measurement signal is disconnected and does not affect the output.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-TV 32 GL
Function
Analogue multifunction signal isolator with simulation and adjustment via terminals and trimmers
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GL
Input types
Unipolar standard signal
Output types
Unipolar standard signal
Supply types
Wide range, DC 20-30V, AC 230V
Design
DIN rail, screw terminals
Device functions
Simulation, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current input
Measuring range
0/4 ... 20 mA
Input resistance
85 Ohm
Voltage input
Measuring range
0/2 ... 10 V
Input resistance
> 100 kOhm
Current output
Output range
0/4 ... 20 mA
Maximum load
500 Ohm
Ripple
50 µA p-p
Voltage output
Output range
0/2 ... 10 V
Minimum load
> 10 kOhm
Ripple
50 mV p-p
Setpoint generation
Front-panel potentiometer
0 ... 100 %
Power supply
AC voltage range
50 ... 253 V AC, 50/60 Hz
DC voltage range
20 ... 253 V DC
Rated AC/DC voltage
230 V AC / 24 V DC
AC/DC power consumption
2.3 VA / 1W
Transfer characteristics
Basic accuracy
< 0.2 % of full scale
Temperature influence
100 ppm/K of full scale
Response time
~ 20 ms
Housing
Dimensions (w×h×d)
18x78x103 mm
IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Weight
~ 100 g
Construction
35 mm DIN rail
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Galvanic isolation, test voltages
Input / output
3.75 kV, 50 Hz (1 min.)
Signal / power supply
4 kV, 50 Hz (1 min.)
Protective circuits
Inputs
Protection against overvoltage
Output
Protection against overvoltage
Power supply unit
Protection against overvoltage and reverse polarity
Note
1) Minor signal deviations may occur during interference.