Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 454 GVF – Signal splitter/isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 454 GVF

Analogue signal splitter/isolator with 4 galvanically isolated output channels

Housing type GVFDIN rail
Input
Standard analogue signal input
Output
4x standard analogue signal output
Power supply
Wide-range power supply
Housing type
GVF
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 454 GVF distributes an analogue measurement signal to four independent outputs, converting or amplifying it if required. Each output is galvanically isolated from the other outputs, the input and the supply, allowing signal types to be selected individually for downstream processing.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 454 GVF
FunctionAnalogue signal splitter/isolator with 4 galvanically isolated output channels
InputStandard analogue signal input
Output4x standard analogue signal output
Power supplyWide-range power supply
Housing typeGVF
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, plug-in terminals, screw terminals
Device functionsStandard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range0 ... 20 mA, 4 ... 20 mA
Input resistance50 Ohm

Voltage input

Measuring range0 ... 10 V, 2 ... 10 V
Input resistance100 kOhm

Current output

Output range0 ... 20 mA, 4 ... 20 mA
Maximum load400 Ohm
Ripple40 µA p-p

Voltage output

Output range0 ... 10 V, 2 ... 10 V
Minimum load10 kOhm
Ripple20 mV p-p

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range21 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption TV 452 GVCMax 3 VA / 2 W
AC/DC power consumption TV 454 GVFMax 5 VA / 4 W

Transfer characteristics

Basic accuracy< 0.2 % of full scale
Temperature influenceMax 50 ppm/K of full scale
Response time~ 20 ms

Housing

Dimensions TV 452 GVC (w×h×d)18x110x134 mm
Dimensions TV 454 GVF (w×h×d)33x110x134 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight TV 452 GVC~ 130 g
Weight TV 454 GVF~ 210 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
AltitudeMax. 2000 m
Pollution degree2

Galvanic isolation, test voltages

Input / output2.5 kV, 50 Hz (1 min.)
Output to output2.5 kV, 50 Hz (1 min.)
Signal / power supply3 kV, 50 Hz (1 min.)

Protective circuits

InputProtection against overvoltage
OutputProtection against overvoltage
Power supply unitProtection against overvoltage and reverse polarity

Note1) Minor signal deviations may occur during interference.

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik