Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 515 GS – AC signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 515 GS

Analogue AC signal isolator with integrated current transformers for standard DC signal output

Housing type GSDIN rail
Input
AC currents
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GS
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 515 GS measures sinusoidal alternating currents using integrated current transformers and converts them into galvanically isolated standard DC signals. It adapts current-transformer signals to downstream measurement systems; external transformers can be connected upstream for higher currents, and signals can be adjusted on the front panel.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 515 GS
FunctionAnalogue AC signal isolator with integrated current transformers for standard DC signal output
InputAC currents
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGS
Input typesAC quantities
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsgalvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Input

Measuring range0 ... 1 A AC / 0 ... 5 A AC
Input frequency40 ... 60 Hz (sinusoidal)
Short-term overload (1 s)20 times the rated value
Continuous overload (24 h)120 % of the rated value

Current output

Maximum output range0/4 ... 20 mA 1)
Maximum load400 Ohm
Ripple50 µA p-p

Voltage output

Maximum output range0 .. 10 V 1)
Minimum load1 kOhm
Ripple30 mV p-p

Transfer characteristics

Linearity errorMax. 0.5 % of full scale
Rise time (10...90 %)Approx. 2 s
Temperature influence+/- 100 ppm/K

Power supply

Supply voltage20 ... 253 V DC / 50 ... 253 V AC
Max. power consumption1.7 W / 3.5 VA

Housing

ConstructionDIN rail (EN 50022)
IP ratingIP 20
Terminal conductor cross-sectionMax. 2.5 mm²
Screw-terminal tightening torque0.5 Nm
Weight~ 110 g

Ambient conditions

Permissible ambient temperature-10 ... 50 °C
Storage and transport-10 ... 60 °C

EMC

Product family standardEN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
AltitudeMax. 2000 m
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III
Max. continuous working voltage300 V AC

Galvanic isolation, test voltages

Input/output4 kV (1 min)
Input/power supply4 kV (1 min)
Output/power supply3 kV (1 min)

Note1) Specify values when ordering.
Note2) Minor signal deviations may occur during interference.
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik