Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 561 GS – AC signal isolator

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 561 GS

Analogue AC signal isolator for sinusoidal mains-voltage signals

Housing type GSDIN rail
Input
AC voltages
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GS
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 561 GS acquires sinusoidal AC voltage signals, rectifies them and converts them into a proportional standard analogue signal. Input, output and supply are galvanically isolated from one another for further processing of mains-voltage signals; the device also provides signal amplification.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 561 GS
FunctionAnalogue AC signal isolator for sinusoidal mains-voltage signals
InputAC voltages
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGS
Input typesAC quantities
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsgalvanic isolation (I/O)
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Input

Measuring range min/max0 ... 30 V AC / 0 ... 600 V AC 1)
Input frequency50 ... 60 Hz, sinusoidal fundamental
Input resistance1 kOhm / V input voltage

Current output

Maximum output range0/4 ... 20 mA 1)
Maximum load500 Ohm

Voltage output

Maximum output range0 .. 10 V 1)
Minimum load1 kOhm

Transfer characteristics

Linearity error0.3 % of full scale at the fundamental frequency
Rise time (10...90%)700 ms
Temperature influence+/- 100 ppm/K
Current rippleMax. 50 µA p-p
Voltage rippleMax. 100 mV p-p

Power supply

Supply voltage20 ... 253 V DC / 50 ... 253 V AC
Max. power consumption1 W / 2.1 VA

Housing

ConstructionDIN rail (EN 50022)
IP ratingIP 20
Terminal conductor cross-sectionMax. 2.5 mm²
Screw-terminal tightening torque0.5 Nm
Weight~ 110 g

Ambient conditions

Permissible ambient temperature-10 ... 50 °C
Storage and transport-10 ... 60 °C

EMC

Product family standardEN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III

Galvanic isolation, test voltages

Input/output4 kV (1 min)
Input/power supply4 kV (1 min)
Output/power supply3 kV (1 min)

Note1) Specify values when ordering.
Note2) Minor signal deviations may occur during interference.
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik