NewAnalogue signal conditioning
AD-LW 110 GVC
Load monitor for cos phi and undervoltage with adjustable limits

Manufacturer image of the device family. The actual version may differ.
Digital AC signal isolator for mains voltages, with true RMS measurement
Price and delivery time on request. Personal advice from Grubatec.
The AD-TV 591 GS measures the true RMS value of AC voltages and converts it into a galvanically isolated standard DC signal. Zero and measuring range can be adjusted to suit the measurement task using selectable front-panel trimmers or the optional AD-Studio configuration software.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-TV 591 GS |
| Function | Digital AC signal isolator for mains voltages, with true RMS measurement |
| Input | AC voltages |
| Output | Standard analogue signal output |
| Power supply | Wide-range power supply |
| Housing type | GS |
| Input types | AC quantities |
| Output types | Unipolar standard signal |
| Supply types | Wide range, DC 20-30V, AC 230V |
| Interface / protocols | AD-UART |
| Design | DIN rail, screw terminals |
| Device functions | galvanic isolation (I/O) |
| Measuring range | 0 ... 250 V AC / 0 ... 450 V AC 1) |
|---|---|
| Input frequency | 40 ... 400 Hz |
| Maximum output range | 0 ... 20 mA 1) |
|---|---|
| Maximum load | 500 Ohm |
| Maximum output range | 0 .. 10 V 1) |
|---|---|
| Minimum load | 10 kOhm |
| Trim range | +/-20 % 1) |
|---|---|
| Linearity error | 0.5 % of full scale |
| Measurement time | 20 ms (1 cycle) |
| Rise time (90%) | 200 ms (min. 60 ms) 3) |
| Response time | 220 ms (min. 80 ms) 3) |
| Temperature influence | +/- 100 ppm/K |
| Supply voltage | 20 ... 253 V DC / 50 ... 253 V AC |
|---|---|
| Max. power consumption | 1.2 W / 2.2 VA |
| Construction | DIN rail (EN 50022) |
|---|---|
| IP rating | IP 20 |
| Terminal conductor cross-section | Max. 2.5 mm² |
| Screw-terminal tightening torque | 0.5 Nm |
| Weight | ~ 120 g |
| Permissible ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 60 °C |
| Product family standard | EN 61326-1 |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Measurement circuit safety | EN 61010-2-030 |
| Measurement category | CAT III |
| Input/output | 4 kV (1 min) |
|---|---|
| Input/power supply | 4 kV (1 min) |
| Output/power supply | 3 kV (1 min) |
| Note | 1) Specify different values when ordering. |
|---|---|
| Note | 2) Minor signal deviations may occur during interference. |
| Note | 3) Filter 5 (Filter 0). |
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.