NewAnalogue signal conditioning
AD-LW 110 GVC
Load monitor for cos phi and undervoltage with adjustable limits

Manufacturer image of the device family. The actual version may differ.
Analogue 1:1 isolating transmitter for converting active signals to a current-sink output
Price and delivery time on request. Personal advice from Grubatec.
The AD-TWT 24 GM galvanically isolates an active 4–20 mA standard signal and transfers it at a 1:1 ratio to a passive transmitter signal. For connection using 2-wire transmitter technology, the required operating power is drawn from the transmitter supply on the output side.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-TWT 24 GM |
| Function | Analogue 1:1 isolating transmitter for converting active signals to a current-sink output |
| Input | Standard analogue signal input |
| Output | Standard analogue signal output (current sink) |
| Power supply | Power supplied through the output (transmitter supply voltage) |
| Housing type | GM |
| Input types | Unipolar standard signal |
| Output types | Unipolar standard signal |
| Supply types | Transmitter |
| Design | DIN rail, screw terminals |
| Device functions | galvanic isolation (I/O), 1:1 standard signal isolation |
| Measuring range | 4 ... 20 mA |
|---|---|
| Input voltage requirement | 2.7 V (4 V at no load) |
| Output range | 4 ... 20 mA |
|---|---|
| Supply voltage | 8 - 30 V DC |
| Ripple | Max. 0.5 % of full scale |
| Basic accuracy | < 0.2 % of full scale |
|---|---|
| Temperature influence | 150 ppm/K of full scale |
| Response time | ~ 700 ms |
| Dimensions (w×h×d) | 13x78x103 mm |
|---|---|
| IP rating | IP 20 |
| Connection technology | Screw terminals |
| Terminal conductor cross-section | 2.5 m² stranded wire / 4 mm² solid wire |
| Terminal tightening torque | 0.5 Nm |
| Weight | ~ 100 g |
| Construction | 35 mm DIN rail |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard | EN 61326-1 1) |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Maximum continuous working voltage across the galvanic isolation | 45 V DC |
| Input / output | 510 V, 50 Hz (1 min.) |
|---|
| Inputs | Protection against overvoltage and reverse polarity |
|---|---|
| Output | Protection against overvoltage |
| Note | 1) Minor signal deviations may occur during interference. |
|---|
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.