Analogue signal conditioning
AD-VC 4S FE-R0
Digital multifunction transmitter for panel mounting, with LCD and analogue outputs

Manufacturer image of the device family. The actual version may differ.
Digital multifunction transmitter with LCD, four relays and standard analogue signal outputs
Price and delivery time on request. Personal advice from Grubatec.
The AD-VC 4S FE-R4 conditions standard analogue and potentiometer signals and provides measured values through an LCD and standard analogue signal outputs. This panel-mount version with four relays is suitable for monitoring up to four freely adjustable limits and can be configured directly on the device or using AD-Studio.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-VC 4S FE-R4 |
| Function | Digital multifunction transmitter with LCD, four relays and standard analogue signal outputs |
| Input | Standard analogue signal input, transmitter power supply, potentiometer |
| Output | Standard analogue signal output, 4x relay |
| Power supply | Wide-range power supply |
| Housing type | FE |
| Input types | Unipolar standard signal, bipolar standard signal, transmitter power supply, multifunction input, potentiometer |
| Output types | Unipolar standard signal, relay |
| Supply types | Wide range, DC 20-30V, AC 230V |
| Interface / protocols | AD-UART |
| Display / operation | LCD |
| Design | Panel mounting, plug-in terminals, screw terminals |
| Device functions | Simulation, freely configurable, limit monitoring, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable |
| Measuring range | 0 ... + 20 mA |
|---|---|
| Accuracy | ~ 21 µA |
| Input resistance | < 51 Ohm |
| Measuring range | -10 ... + 10 V |
|---|---|
| Accuracy | ~ 21 mV |
| Input resistance | 100 kOhm |
| Measuring range | -5 ... + 5 V |
|---|---|
| Accuracy | ~ 11 mV |
| Input resistance | 100 kOhm |
| Measuring range | -1 ... + 1 V |
|---|---|
| Accuracy | ~ 2.5 mV |
| Input resistance | 100 kOhm |
| Measuring range | -100 ... + 100 mV |
|---|---|
| Accuracy | ~ 0.3 mV |
| Input resistance | 100 kOhm |
| Connection technology | 3-wire |
|---|---|
| Permissible total resistance | > 100 Ohm |
| No-load supply voltage | ~ 23 V |
|---|---|
| Supply voltage at 20mA | ~ 21 V |
| Current limitation | ~ 55 mA |
| Maximum output range | 0 ... 20 mA |
|---|---|
| Accuracy | ~ 20 µA |
| Maximum load | 500 Ohm |
| Ripple | 20 µA p-p |
| Variants | R2, R4 |
|---|---|
| Maximum output range | 0 ... 10 V |
| Accuracy | ~ 10 mV |
| Minimum load | 10 kOhm |
| Ripple | 10 mV p-p |
| Input | 10 bit |
|---|---|
| Output | 10 bit |
| Contacts R2 / R4 | 2 changeover contacts / 4 changeover contacts |
|---|---|
| Max. AC switching capacity | 250 V AC, 2 A AC, 50Hz |
| Max. DC switching capacity | 50 V DC, 2 A DC |
| Note | Switching cycles |
| Mechanical | 107 |
| AC: 230V / 2A, cos(phi)=1 | 6 * 105 |
| AC: 230V / 2A, cos(phi)=0.4 | 2 * 105 |
| DC: 24V / 1A | 2 * 105 |
| DC: 24V / 1A | 2 * 105 |
| Graphic LCD | 122x32 pixels, backlit |
|---|---|
| Digital display | 5-digit, configurable |
| Display function | Scaled input signal, input signal, outputs, limits, scaled value as a bar graph, scaling unit |
| Linearity error | < 0.2 % of full scale |
|---|---|
| Rise time | 100 ms (output at 90%) |
| Temperature influence | +/- 100 ppm/K of full scale |
| Supply voltage | 20 ... 253 V DC / 50 ... 253 V AC |
|---|---|
| Max. power consumption | 2.6 W / 5 VA |
| Construction | Panel-mount housing (DIN 43 700) |
|---|---|
| Front IP rating | IP 65 |
| Housing IP rating | IP 20 |
| Terminal conductor cross-section | 1.0 mm² stranded wire with ferrule / 1.5 mm² solid wire |
| Supply terminal conductor cross-section | Max. 2.5 mm² |
| Weight | ~ 320 g |
| Panel cut-out | 92 x 44 mm |
| Permissible ambient temperature | -10 ... 60 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard 1) | EN 61326-1 |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Note | 1) Minor signal deviations may occur during interference. |
| Product family standard | EN 61010-1 |
|---|
| Input/output | 2.5 kV (1 min) |
|---|---|
| Signal/power supply | 4 kV (1 min) |
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.