Back to pulse & frequency
Product image of the device family – Grubatec – AD-KI 10 GX – Contact-protection pulse relay

Manufacturer image of the device family. The actual version may differ.

Pulses & frequency

AD-KI 10 GX

Slim contact-protection pulse relay for amplifying and shaping binary sensor signals

Housing type GXDIN rail
Input
Frequency or pulse input
Output
Relay
Power supply
24V DC
Housing type
GX
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-KI 10 GX protects low-power sensor contacts and converts binary input signals into adjustable-duration pulses for its volt-free relay contact. Its slim design allows compact installation, for example when acquiring water meter pulses or transmitting switching signals.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-KI 10 GX
FunctionSlim contact-protection pulse relay for amplifying and shaping binary sensor signals
InputFrequency or pulse input
OutputRelay
Power supply24V DC
Housing typeGX
Input typesPulses, NAMUR signals, optical sensors
Output typesRelay, S0, pulses
Supply typesDC 20-30V
DesignDIN rail, screw terminals, 6.3 mm width
Device functionsgalvanic isolation (I/O), quantity pulses, energy pulses
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Pulse input

NAMUR supply voltage~ 8.2 V DC
Logic levels for NAMUR signalsLow / High: 2.1 mA / 1.2 mA
Logic levels for active signalsLow / High: 9.5 V / 11.5 V
Max. input voltage30 V DC
Contact8 mA
Pulse width1 ms ... infinite

Pulse processing

Output pulse duration0.2 ... 10 s

Relay output

Maximum AC switching load250 V, 2 A
Maximum DC switching load50 V, 2 A
Contact configurationVolt-free normally open contact
Mechanical switching cycles10000000
At 230V/2A AC, cos(phi)=1600000
At 230V/2A AC, cos(phi)=0.4200000
At 24V/1 A DC200000

Power supply

DC voltage range18 ... 30 V DC
Rated DC voltage24 V DC
DC power consumption700 mW

Housing

Dimensions (W×H×D)6.2 x 92 x 101 mm³
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 70 g
ConstructionDIN rail 35mm, EN 50022

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... +70 °C (avoid condensation)

EMC

Product family standard 1)EN 61326-1
Emissions 2)EN 55011, CISPR11 class A, group 1
Note1) Minor signal deviations may occur during interference.
Note2) Warning: This equipment is not intended for use in residential environments and may not provide adequate protection for radio reception in such environments.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Signal / power supply1.5 kV, 50 Hz (1 min)
Contact3 kV, 50 Hz (1 min)

Protective circuits

InputsProtection against overvoltage
Power supply unitProtection against overvoltage, overtemperature and reverse polarity

Note1) Minor signal deviations may occur during interference.
Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik