Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-KI 10 GX protects low-power sensor contacts and converts binary input signals into adjustable-duration pulses for its volt-free relay contact. Its slim design allows compact installation, for example when acquiring water meter pulses or transmitting switching signals.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-KI 10 GX
Function
Slim contact-protection pulse relay for amplifying and shaping binary sensor signals
Input
Frequency or pulse input
Output
Relay
Power supply
24V DC
Housing type
GX
Input types
Pulses, NAMUR signals, optical sensors
Output types
Relay, S0, pulses
Supply types
DC 20-30V
Design
DIN rail, screw terminals, 6.3 mm width
Device functions
galvanic isolation (I/O), quantity pulses, energy pulses
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Pulse input
NAMUR supply voltage
~ 8.2 V DC
Logic levels for NAMUR signals
Low / High: 2.1 mA / 1.2 mA
Logic levels for active signals
Low / High: 9.5 V / 11.5 V
Max. input voltage
30 V DC
Contact
8 mA
Pulse width
1 ms ... infinite
Pulse processing
Output pulse duration
0.2 ... 10 s
Relay output
Maximum AC switching load
250 V, 2 A
Maximum DC switching load
50 V, 2 A
Contact configuration
Volt-free normally open contact
Mechanical switching cycles
10000000
At 230V/2A AC, cos(phi)=1
600000
At 230V/2A AC, cos(phi)=0.4
200000
At 24V/1 A DC
200000
Power supply
DC voltage range
18 ... 30 V DC
Rated DC voltage
24 V DC
DC power consumption
700 mW
Housing
Dimensions (W×H×D)
6.2 x 92 x 101 mm³
IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque
0.5 Nm
Weight
~ 70 g
Construction
DIN rail 35mm, EN 50022
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... +70 °C (avoid condensation)
EMC
Product family standard 1)
EN 61326-1
Emissions 2)
EN 55011, CISPR11 class A, group 1
Note
1) Minor signal deviations may occur during interference.
Note
2) Warning: This equipment is not intended for use in residential environments and may not provide adequate protection for radio reception in such environments.
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Galvanic isolation, test voltages
Signal / power supply
1.5 kV, 50 Hz (1 min)
Contact
3 kV, 50 Hz (1 min)
Protective circuits
Inputs
Protection against overvoltage
Power supply unit
Protection against overvoltage, overtemperature and reverse polarity
Note
1) Minor signal deviations may occur during interference.