Back to analogue signal processing
Product image of the device family – Grubatec – AD-TV 411 GS – Signal isolator for standard current signals

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-TV 411 GS

Single-channel analogue 1:1 signal isolator for standard current signals

Housing type GSDIN rail
Input
Standard analogue signal input
Output
Standard analogue signal output
Power supply
Wide-range power supply
Housing type
GS
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-TV 411 GS transfers an impressed direct current at a 1:1 ratio and galvanically isolates input, output and supply. This single-channel version boosts the load capacity of a current signal and supports different supply voltages thanks to its integrated wide-range power supply.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-TV 411 GS
FunctionSingle-channel analogue 1:1 signal isolator for standard current signals
InputStandard analogue signal input
OutputStandard analogue signal output
Power supplyWide-range power supply
Housing typeGS
Input typesUnipolar standard signal
Output typesUnipolar standard signal
Supply typesWide range, DC 20-30V, AC 230V
DesignDIN rail, screw terminals
Device functionsgalvanic isolation (I/O), 1:1 standard signal isolation
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range0 ... 20 mA or 4 ... 20 mA
Input voltage requirementApprox. 0.8 V

Current output

Output range0 ... 20 mA or 4 ... 20 mA
Maximum load500 Ohm
Ripple40 µA p-p

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
Rated AC voltage230 V AC
DC voltage range20 ... 253 V DC
Rated DC voltage24 V DC
AC/DC power consumption (AD-TV 411 GS)4.5 VA / 1.5 W
AC/DC power consumption (AD-TV 412 GS)5 VA, 2.5 W

Transfer characteristics

Basic accuracy< 0,2 %
Temperature influence15 ppm/K
Response time0.2 ms
Load influence0.02 % / 100 Ohm

Housing

Dimensions (w×h×d)23x78x103 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 160 g
Construction35 mm DIN rail

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input / output0.5 kV, 50 Hz (1 min.)
Signal / power supply3 kV, 50 Hz (1 min.)
Channel 1 / channel 2 (TV 412 GS)0.5 kV, 50 Hz (1 min.)

Protective circuits

InputsProtection against overvoltage
OutputProtection against overvoltage
Power supply unitProtection against overvoltage, reverse polarity, overtemperature and overcurrent

Note1) Minor signal deviations may occur during interference.

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik