Analogue signal conditioning
AD-TV 411 GS
Single-channel analogue 1:1 signal isolator for standard current signals

Manufacturer image of the device family. The actual version may differ.
Two-channel analogue 1:1 signal isolator with mutually isolated channels
Price and delivery time on request. Personal advice from Grubatec.
The AD-TV 412 GS isolates and amplifies standard current signals through two channels whose outputs follow their respective inputs at a 1:1 ratio. The channels are also galvanically isolated from one another for processing separate measurement circuits; power is provided through an integrated wide-range power supply.
| Manufacturer | Adamczewski Elektronische Messtechnik GmbH |
|---|---|
| Model | AD-TV 412 GS |
| Function | Two-channel analogue 1:1 signal isolator with mutually isolated channels |
| Input | Standard analogue signal input |
| Output | Standard analogue signal output |
| Power supply | Wide-range power supply |
| Housing type | GS |
| Input types | Unipolar standard signal |
| Output types | Unipolar standard signal |
| Supply types | Wide range, DC 20-30V, AC 230V |
| Design | DIN rail, screw terminals |
| Device functions | galvanic isolation (I/O), 1:1 standard signal isolation |
| Measuring range | 0 ... 20 mA or 4 ... 20 mA |
|---|---|
| Input voltage requirement | Approx. 0.8 V |
| Output range | 0 ... 20 mA or 4 ... 20 mA |
|---|---|
| Maximum load | 500 Ohm |
| Ripple | 40 µA p-p |
| AC voltage range | 50 ... 253 V AC, 50/60 Hz |
|---|---|
| Rated AC voltage | 230 V AC |
| DC voltage range | 20 ... 253 V DC |
| Rated DC voltage | 24 V DC |
| AC/DC power consumption (AD-TV 411 GS) | 4.5 VA / 1.5 W |
| AC/DC power consumption (AD-TV 412 GS) | 5 VA, 2.5 W |
| Basic accuracy | < 0,2 % |
|---|---|
| Temperature influence | 15 ppm/K |
| Response time | 0.2 ms |
| Load influence | 0.02 % / 100 Ohm |
| Dimensions (w×h×d) | 23x78x103 mm |
|---|---|
| IP rating | IP 20 |
| Connection technology | Removable screw terminals |
| Terminal conductor cross-section | 2.5 mm² stranded wire / 4 mm² solid wire |
| Terminal tightening torque | 0.5 Nm |
| Weight | ~ 160 g |
| Construction | 35 mm DIN rail |
| Ambient temperature | -10 ... 50 °C |
|---|---|
| Storage and transport | -10 ... 70 °C (avoid condensation) |
| Product family standard | EN 61326-1 1) |
|---|---|
| Emissions | EN 55011, CISPR11 class B, group 1 |
| Product family standard | EN 61010-1 |
|---|---|
| Overvoltage category | II |
| Pollution degree | 2 |
| Input / output | 0.5 kV, 50 Hz (1 min.) |
|---|---|
| Signal / power supply | 3 kV, 50 Hz (1 min.) |
| Channel 1 / channel 2 (TV 412 GS) | 0.5 kV, 50 Hz (1 min.) |
| Inputs | Protection against overvoltage |
|---|---|
| Output | Protection against overvoltage |
| Power supply unit | Protection against overvoltage, reverse polarity, overtemperature and overcurrent |
| Note | 1) Minor signal deviations may occur during interference. |
|---|
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.
Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.