Product image of the device family – Grubatec – AD-VC 1 GVF-R4 – Multifunction transmitter

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-VC 1 GVF-R4

Digital multifunction transmitter with four relays for standard and temperature signals

Housing type GVDDIN rail
Input
Standard analogue signal input, transmitter power supply, potentiometer, RTD, PT, NI, thermocouples, mV
Output
Standard analogue signal output, 4x relay
Power supply
Wide-range power supply
Housing type
GVD
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-VC 1 GVF-R4 acquires standard and temperature signals and provides four relays for signal monitoring in addition to standard analogue signal outputs. Freely adjustable limit or window functions support different switching conditions; measuring ranges and outputs are configured using AD-Studio or the optional AD-VarioControl.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-VC 1 GVF-R4
FunctionDigital multifunction transmitter with four relays for standard and temperature signals
InputStandard analogue signal input, transmitter power supply, potentiometer, RTD, PT, NI, thermocouples, mV
OutputStandard analogue signal output, 4x relay
Power supplyWide-range power supply
Housing typeGVD
Input typesUnipolar standard signal, temperature, transmitter power supply, multifunction input, mV-DC, potentiometer, resistance
Output typesUnipolar standard signal, bipolar standard signal, relay
Supply typesWide range, DC 20-30V, AC 230V
Interface / protocolsAD-UART
Display / operationclip-on display
DesignDIN rail, plug-in terminals, screw terminals
Device functionsSimulation, freely configurable, limit monitoring, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range-24 ... + 24 mA DC
Input resistance20 Ohm
Basic accuracy4 µA

Transmitter power supply

No-load supply voltage24.0 V
Supply voltage at 20mA18.0 V
Current limitation~ 25 mA

Voltage input

Measuring ranges0 ... + 12 V DC
Input resistance1 MOhm
Basic accuracy1 mV

Voltage input mV 1)

Measuring ranges-15 ... +15 mV
-30 ... +30 mV
-60 ... +60 mV
-125 ... +125 mV
-250 ... +250 mV
Input resistance1 MOhm
Basic accuracy20 µV

Thermocouples

NoteCold junction:
InternalMeasurement with a sensor at the internal device terminals
ExternalCold-junction temperature selectable via parameter
NoteAccording to DIN EN 60584:
Measuring range type J-200 ... +1200 °C
Measuring range type T-200 ... +400 °C
Measuring range type K-200 ... +1360 °C
Measuring range type E-200 ... +1000 °C
Measuring range type N-200 ... +1300 °C
Basic accuracy1 K
NoteAccording to DIN EN 60584:
Measuring range type S-40 ... +1760 °C
Measuring range type R-40 ... +1760 °C
Measuring range type B+400 ... +1800 °C
Basic accuracy2 K
NoteAccording to ASTM standard E988:
Measuring range type C0 ... +2320 °C
Basic accuracy2 K

Resistance input 1)

NoteResistance thermometers DIN EN 60751: Pt100, Pt500 and Pt1000 DIN 43760: Ni100, Ni500 and Ni1000
Measuring range Pt-200 ... +850 °C
Measuring range Ni-60 ... +230 °C
Minimum measurement span20 K
Short-circuit detection< 20 Ohm
Basic accuracy0.2 K
NoteLinear resistance
Measuring range0 ... 4000 Ohm
Basic accuracy0.1 Ohm
NoteNot specified
Connection technology2-wire, 3-wire or 4-wire
Sensor power supply100 µA
Max. lead resistance 2)50 Ohm/conductor

Potentiometer input

Connection technology3-wire
Permissible total resistance50 Ohm ... 100 kOhm
Sensor power supply<=500µA
Cable length< 30 m, must remain within the building

Current outputs

Maximum output range-21.5 ... 21.5 mA DC
Maximum load400 Ohm
Ripple20 µA p-p

Voltage outputs

Maximum output range-10.5 ... 10.5 V DC
Minimum load10 kOhm
Ripple10 mV p-p

Relay outputs A...D

Contacts R2 / R42 changeover contacts / 4 changeover contacts
Max. AC switching capacity250 V AC, 2 A AC, 50Hz
Max. DC switching capacity40 V DC, 2 A DC
NoteSwitching cycles
Mechanical107
AC: 230V / 2A, cos(phi)=16 * 105
AC: 230V / 2A, cos(phi)=0.42 * 105
DC: 24V / 1A2 * 105

Transfer characteristics

Linearity error< 0.2 % of the measuring range
Temperature influence+/- 120 ppm/K of the measuring range
Rise time500 ms (0...90 %, 100...10 %)
Rise time (temperature input)< 1s (0...90 %, 100...10 %)

Power supply

AC voltage range50 ... 253 V AC, 50/60 Hz
DC voltage range20 ... 253 V DC
Rated AC/DC voltage230 V AC / 24 V DC
AC/DC power consumption5.4 VA / 3.4 W
AC/DC power consumption with operating module5.6 VA / 3.8 W

Housing GVD

Dimensions (w×h×d)23x110x134 mm
With operating module (w×h×d)23x110x138 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 150 g
Construction35 mm DIN rail

Housing GVF

Dimensions (w×h×d)33x110x134 mm
With operating module (w×h×d)33x110x138 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 200 g
Construction35 mm DIN rail

Ambient conditions

Permissible ambient temperature-10 ... 70 °C
Storage and transport-20 ... 70 °C (avoid condensation)

EMC

Product family standard 3)EN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

IP rating2 (EN 60529)
Product family standardEN 61010-1
Overvoltage categoryII
AltitudeMax. 2000 m
Pollution degree2

Galvanic isolation, working voltages 4)

Input / output300 V DC or AC RMS EN 61010-1: table 6/7 5) 6)
Input / power supply300 V DC or AC RMS EN 61010-1: table 4 5)
Output / power supply300 V DC or AC RMS EN 61010-1: table 4 5)

Galvanic isolation, test voltages

Input / output2.5 kV, 50 Hz / 1 min.EN 61010-1: table 6/7 5) 6)
Input / power supply4 kV, 50 Hz / 1 min.EN 61010-1: table 5 5)
Output / power supply4 kV, 50 Hz / 1 min.EN 61010-1: table 5 5)

Note1) Use a screened cable for the connection.
Note2) With a 2-wire connection, lead resistance introduces an offset into the measurement.
Note3) Minor signal deviations may occur during interference.
Note4) Maximum voltage continuously applied across the insulation.
Note5) Double or reinforced insulation.
Note6) Maximum continuous input-side common-mode voltage relative to earth potential: 50 V AC RMS or 120 V DC

Other versions.