Back to analogue signal processing
Product image of the device family – Grubatec – AD-VC 3 GF-R2 – Multifunction transmitterDiscontinued

Manufacturer image of the device family. The actual version may differ.

Analogue signal conditioning

AD-VC 3 GF-R2

Multifunction transmitter with LCD, analogue outputs and 2 relays for standard signals

Housing type GFDIN rail
Input
Standard analogue signal input, transmitter power supply, potentiometer
Output
Standard analogue signal output, 2x relay
Power supply
Wide-range power supply
Housing type
GF
Marked by the manufacturer as no longer available.
Ask us about a suitable replacement solution.
Datasheet (EN)

Advice on a successor model from Grubatec.

Model overview.

The AD-VC 3 GF-R2 processes standard analogue signals and combines an LCD measurement display with analogue outputs and two relays for limit monitoring. An integrated simulation mode supports checking of signal processing; settings can be made directly on the device or using the AD-Studio PC software.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-VC 3 GF-R2
FunctionMultifunction transmitter with LCD, analogue outputs and 2 relays for standard signals
InputStandard analogue signal input, transmitter power supply, potentiometer
OutputStandard analogue signal output, 2x relay
Power supplyWide-range power supply
Housing typeGF
Input typesUnipolar standard signal, bipolar standard signal, transmitter power supply, multifunction input, high DC voltages, potentiometer, resistance
Output typesUnipolar standard signal, relay
Supply typesWide range, DC 20-30V, AC 230V
Interface / protocolsAD-UART
Display / operationLCD
DesignDIN rail, screw terminals
Device functionsSimulation, freely configurable, limit monitoring, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current input

Measuring range-20 ... + 20 mA
Accuracy5 µA
Input resistance60 Ohm

Voltage input 10V

Measuring range-10 ... + 10 V
Accuracy2.5 mV
Input resistance1 MOhm

Voltage input 1V

Measuring range-1 ... + 1 V
Accuracy250 µV
Input resistance> 1 MOhm

Potentiometer input

Connection technology3-wire
Permissible total resistance100 Ohm ... 100 kOhm

Transmitter power supply

No-load supply voltage24.5 V
Supply voltage at 20mA19.5 V
Current limitation~ 25 mA

Current output

Maximum output range0 ... 20.4 mA
Accuracy~ 20 µA
Maximum load500 Ohm
Ripple20 µA p-p

Voltage output

Maximum output range0 ... 10.2 V (EV: 12.5 V)
Accuracy~ 10 mV
Minimum load5 kOhm
Ripple10 mV p-p

Resolution

Input13 bit
Output10 bit

Relay outputs A...D

Contacts R2 / R42 changeover contacts / 4 changeover contacts
Max. AC switching capacity250 V AC, 2 A AC, 50Hz
Max. DC switching capacity50 V DC, 2 A DC
NoteSwitching cycles
Mechanical107
AC: 230V / 2A, cos(phi)=16 * 105
AC: 230V / 2A, cos(phi)=0.42 * 105
DC: 24V / 1A2 * 105
DC: 24V / 1A2 * 105

Display

Graphic LCD42x64 pixels, RGB backlight
Digital display4-digit, configurable
Display functionScaled input signal, input signal, outputs, limits, scaled value as a bar graph, scaling unit

Transfer characteristics

Linearity error0.2 % of full scale
Rise time100 ms (output at 90%)
Temperature influence+/- 100 ppm/K of full scale

Power supply

Supply voltage GF/GVF20 ... 253 V DC / 50 ... 253 V AC
Supply voltage EV20..30 VDC or 50...253 VAC
Max. power consumption GF3.0 W / 5.3 VA
Max. power consumption GVF2.6 W / 5 VA
Max. power consumption EV2.6 W / 5 VA

Housing GF

Dimensions (w×h×d)38.5x78x103 mm
IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 215 g
Construction35 mm DIN rail

Housing GVF

Dimensions (w×h×d)33x110x134 mm
IP ratingIP 20
Connection technologyRemovable screw terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Terminal tightening torque0.5 Nm
Weight~ 200 g
Construction35 mm DIN rail

Housing EV

Dimensions (w×h×d)30.48x128.4x165
IP ratingIP00
Connection technology32-pin male connector
Weight~ 300 g
Construction19"-Eurocard

Ambient conditions

Permissible ambient temperature-10 ... 60 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standard 1)EN 61326-1
EmissionsEN 55011, CISPR11 class B, group 1
Note1) Minor signal deviations may occur during interference.

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

Galvanic isolation, test voltages

Input/output2.5 kV (1 min)
Signal/power supply3 kV (1 min)

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik