Price and delivery time on request. Personal advice from Grubatec.
Model overview.
The AD-LU 60 FE-B combines three-phase power measurement using integrated current transformers with a colour TFT display for panel mounting. The RS485 interface with Modbus RTU allows measured values and counters to be read and device parameters to be configured when local indication is to be integrated into a data polling system.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-LU 60 FE-B
Function
Three-phase digital power meter with integrated current transformers, TFT display and RS485
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Current inputs
Measuring ranges
0 ... 1/5/20 A AC
Maximum conductor diameter
4.8 mm²
Voltage inputs/power supply
Rated voltage
230 V AC
Rated frequency
50 Hz
Frequency range
40 ... 100 Hz
Measuring range
80 ... 253 V AC
Max. power consumption
4 VA
RS485 interface (-B, -DB)
Software protocol
Modbus-RTU
Data format
19200, e, 8, 1
Max. bus nodes
32
Max. bus length
500 m (no spur lines)
Conductor
Twisted and screened
Optocoupler outputs (-D, -DB)
Max. switching voltage, switching current
30 V DC, 50 mA DC
Display
Type
TFT
Resolution
320x240 pixels
Accuracy
Class
0,5
Temperature influence
100 ppm/K
Housing
Dimensions (w×h×d)
96x96x64 mm
Panel cut-out (w×h)
92x92 mm
Front IP rating
IP 54
Housing IP rating
IP 20
Connection technology
Screw terminals
Terminal conductor cross-section
2.5 mm² stranded wire / 4 mm² solid wire
Weight
~ 250 g
Construction
Panel mounting
Ambient conditions
Ambient temperature
-10 ... 50 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard
EN 61326-1 1)
Emissions
EN 55011, CISPR11 class B, group 1
Electrical safety
Product family standard
EN 61010-1
Overvoltage category
II
Pollution degree
2
Measurement circuit safety
EN 61010-2-030
Measurement category
CAT III
Galvanic isolation, test voltages
Mains side to RS485 bus
4 kV, 50 Hz (1 min.)
Mains side to controls
4 kV, 50 Hz (1 min.)
Protective circuits
Voltage inputs
PTC thermistor
RS485 bus
Protection against overvoltage
Optocoupler outputs
Protection against overvoltage
Note
1) Minor signal deviations may occur during interference.
Other versions.
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.