Back to power & energy
Product image of the device family – Grubatec – AD-LU 60 FE-DB – Digital power meter

Manufacturer image of the device family. The actual version may differ.

Power & energy

AD-LU 60 FE-DB

Three-phase digital power meter with TFT display, RS485 and solid-state outputs

Housing type FERS485 bus
Input
3x AC voltage and 3x AC current
Output
Solid-state outputs
Power supply
Power supplied from the measured voltage
Housing type
FE
Datasheet (EN)

Price and delivery time on request. Personal advice from Grubatec.

Model overview.

The AD-LU 60 FE-DB measures three-phase network quantities using integrated current transformers and displays them on a colour TFT screen in a panel-mounted unit. The combination of Modbus RTU over RS485 and two solid-state outputs allows measured values to be queried and limit alarms or energy pulses to be output.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-LU 60 FE-DB
FunctionThree-phase digital power meter with TFT display, RS485 and solid-state outputs
Input3x AC voltage and 3x AC current
OutputSolid-state outputs
Power supplyPower supplied from the measured voltage
Housing typeFE
Input typesPower/energy, AC quantities
Output typesSolid-state switch, S0, pulses
Supply typesWide range, AC 230V
Interface / protocolsAD-UART, RS485 bus, Modbus-RTU
Display / operationTFT
DesignPanel mounting, plug-in terminals, screw terminals
Device functionsfreely configurable, limit monitoring, energy pulses, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Current inputs

Measuring ranges0 ... 1/5/20 A AC
Maximum conductor diameter4.8 mm²

Voltage inputs/power supply

Rated voltage230 V AC
Rated frequency50 Hz
Frequency range40 ... 100 Hz
Measuring range80 ... 253 V AC
Max. power consumption4 VA

RS485 interface (-B, -DB)

Software protocolModbus-RTU
Data format19200, e, 8, 1
Max. bus nodes32
Max. bus length500 m (no spur lines)
ConductorTwisted and screened

Optocoupler outputs (-D, -DB)

Max. switching voltage, switching current30 V DC, 50 mA DC

Display

TypeTFT
Resolution320x240 pixels

Accuracy

Class0,5
Temperature influence100 ppm/K

Housing

Dimensions (w×h×d)96x96x64 mm
Panel cut-out (w×h)92x92 mm
Front IP ratingIP 54
Housing IP ratingIP 20
Connection technologyScrew terminals
Terminal conductor cross-section2.5 mm² stranded wire / 4 mm² solid wire
Weight~ 250 g
ConstructionPanel mounting

Ambient conditions

Ambient temperature-10 ... 50 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standardEN 61326-1 1)
EmissionsEN 55011, CISPR11 class B, group 1

Electrical safety

Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Measurement circuit safetyEN 61010-2-030
Measurement categoryCAT III

Galvanic isolation, test voltages

Mains side to RS485 bus4 kV, 50 Hz (1 min.)
Mains side to controls4 kV, 50 Hz (1 min.)

Protective circuits

Voltage inputsPTC thermistor
RS485 busProtection against overvoltage
Optocoupler outputsProtection against overvoltage

Note1) Minor signal deviations may occur during interference.

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.

Personal. Technical. Solution-focused.

Your measurement task deserves
the right solution.

Unsure about the input signal, output or version? Describe your application to us. Together, we will find the appropriate Adamczewski device.

+41 55 617 00 80
GRUBATEC Mess- und Regeltechnik