The AD-VC 5 GVF-R2 combines temperature-signal processing with an LCD, standard analogue signal outputs and two relays. Limit, window or trend functions can be assigned to the relays for measurement-signal monitoring; configuration is possible on the device or using the AD-Studio PC software.
Manufacturer
Adamczewski Elektronische Messtechnik GmbH
Model
AD-VC 5 GVF-R2
Function
Digital temperature transmitter with LCD, two relays and standard analogue signal outputs
Input
RTD, PT, NI, thermocouples, mV
Output
Standard analogue signal output, 2x relay
Power supply
Wide-range power supply
Housing type
GVF
Input types
Temperature, mV-DC
Output types
Unipolar standard signal, relay
Supply types
Wide range, DC 20-30V, AC 230V
Interface / protocols
AD-UART
Display / operation
LCD
Design
DIN rail, plug-in terminals, screw terminals
Device functions
Simulation, freely configurable, limit monitoring, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.
Resistance thermometers Pt100, Pt500, Pt1000 to DIN EN 60751
Measuring range
-200 ... +850 °C
Connection technology
2-wire, 3-wire or 4-wire
Resolution
16 bit
Accuracy
0.5 K
Minimum measurement span
20 K
Max. lead resistance 1)
10 Ohm/conductor
Note
Sensor power supply
Pt100
1 mA
Pt500, Pt1000
210 µA
Note
1) With a 2-wire connection, lead resistance introduces an offset into the measurement.
Resistance thermometers Ni100, Ni500 and Ni1000 to DIN 43760
Measuring range
-60 ... +230 °C
Connection technology
2-wire, 3-wire or 4-wire
Resolution
16 bit
Accuracy
0.5 K
Minimum measurement span
20 K
Max. lead resistance 1)
10 Ohm/conductor
Note
Sensor power supply
Ni100
1 mA
Ni500, Ni1000
210 µA
Note
1) With a 2-wire connection, lead resistance introduces an offset into the measurement.
Thermocouples
Note
Cold junction:
Internal
Measurement with LM35 at the device terminals
External
Cold-junction temperature selectable via parameter
Resolution
16 bit
Accuracy
0.2 % of the measuring range
Measuring range type J
-200 ... +1200 °C
Note
According to DIN EN 60584:
Measuring range type T
-200 ... +400 °C
Measuring range type K
-200 ... +1360 °C
Measuring range type E
-200 ... +1000 °C
Measuring range type N
-200 ... +1300 °C
Measuring range type S
-40 ... +1760 °C
Measuring range type R
-40 ... +1760 °C
Measuring range type B
+400 ... +1800 °C
Note
According to ASTM standard E988:
Measuring range type C
0 ... +2320 °C
Minimum measurement span
100 K
Voltage inputs
Measuring ranges
-18 ... +18 mV
-36 ... +36 mV
-72 ... +72 mV
-144 ... +144 mV
Current output 20 mA
Output range
0 ... 20.4 mA
Resolution
10 bit
Accuracy
20 µA
Maximum load
500 Ohm
Ripple
20 µA p-p
Voltage output 10 V
Output range
0 ... 10.2 V
Resolution
10 bit
Accuracy
10 mV
Minimum load
5 kOhm
Ripple
10 mV p-p
Note
When current and voltage outputs are used simultaneously, the two circuits must not be connected together.
Relay outputs A..D
Max. switching voltage
AC 250 V AC
Max. AC switching current
2 A AC
Max. switching voltage
DC 50 V DC
Max. DC switching current
2 A DC
Display
Graphic LCD
42x64 pixels, RGB backlight
Digital display
4-digit, configurable
Display function
Scaled input signal, input signal, outputs, limits, scaled value as a bar graph, scaling unit
Transfer characteristics
Measurement rate
1 measurement/s
Linearity error
0.2 % of full scale
Temperature influence
+/-100 ppm/K of full scale
Power supply
Supply voltage
50 ... 253 V AC
20 ... 253 V DC
Max. power consumption at 24V DC
2.6 W
Max. power consumption at 230V AC
5 VA
Housing
Dimensions
W×H×D 33x110x128 mm
Construction
DIN rail 35mm, EN 50022
IP rating
IP 20
Connection technology
Removable screw terminals, 5 mm pitch
Conductor cross-section
Max. 2.5 mm2
Weight
~ 200 g
Ambient conditions
Permissible ambient temperature
-10 ... +60 °C
Storage and transport
-10 ... 70 °C (avoid condensation)
EMC
Product family standard 1)
EN 61326-1
Emissions
EN 55011, CISR11 class B, group 1
Note
1) Minor signal deviations may occur during testing.
Electrical safety
Product family standard
EN 61010-1
Galvanic isolation, test voltages
Input to outputs
2.5 kV, 1min
Input/outputs to auxiliary supply
4 kV, 1min
Between outputs
No galvanic isolation
Input to programming interface
No galvanic isolation
Other versions.
Models in the same device family. Differences may include inputs and outputs, power supply or housing type.