Digital temperature transmitter with LCD, four relays and analogue outputs

Housing type GVFDIN rail
Input
RTD, PT, NI, thermocouples, mV
Output
Standard analogue signal output, 4x relay
Power supply
Wide-range power supply
Housing type
GVF
Marked by the manufacturer as no longer available.
Ask us about a suitable replacement solution.
Datasheet (EN)

Advice on a successor model from Grubatec.

Model overview.

The AD-VC 5 GVF-R4 converts temperature or mV signals into standard analogue signals and shows the measured value on an LCD. Four relays allow multiple switching conditions to be monitored, with a limit, window or trend function configurable for each relay.

ManufacturerAdamczewski Elektronische Messtechnik GmbH
ModelAD-VC 5 GVF-R4
FunctionDigital temperature transmitter with LCD, four relays and analogue outputs
InputRTD, PT, NI, thermocouples, mV
OutputStandard analogue signal output, 4x relay
Power supplyWide-range power supply
Housing typeGVF
Input typesTemperature, mV-DC
Output typesUnipolar standard signal, relay
Supply typesWide range, DC 20-30V, AC 230V
Interface / protocolsAD-UART
Display / operationLCD
DesignDIN rail, plug-in terminals, screw terminals
Device functionsSimulation, freely configurable, limit monitoring, standard signal conversion, galvanic isolation (I/O), 1:1 standard signal isolation, setpoint generation, freely scalable
Further technical data for the device family
These details come from the manufacturer’s shared page for the device family. Where several versions exist, individual values apply only to the variant specified. The data sheet for your particular version is authoritative.

Resistance thermometers Pt100, Pt500, Pt1000 to DIN EN 60751

Measuring range-200 ... +850 °C
Connection technology2-wire, 3-wire or 4-wire
Resolution16 bit
Accuracy0.5 K
Minimum measurement span20 K
Max. lead resistance 1)10 Ohm/conductor
NoteSensor power supply
Pt1001 mA
Pt500, Pt1000210 µA
Note1) With a 2-wire connection, lead resistance introduces an offset into the measurement.

Resistance thermometers Ni100, Ni500 and Ni1000 to DIN 43760

Measuring range-60 ... +230 °C
Connection technology2-wire, 3-wire or 4-wire
Resolution16 bit
Accuracy0.5 K
Minimum measurement span20 K
Max. lead resistance 1)10 Ohm/conductor
NoteSensor power supply
Ni1001 mA
Ni500, Ni1000210 µA
Note1) With a 2-wire connection, lead resistance introduces an offset into the measurement.

Thermocouples

NoteCold junction:
InternalMeasurement with LM35 at the device terminals
ExternalCold-junction temperature selectable via parameter
Resolution16 bit
Accuracy0.2 % of the measuring range
Measuring range type J-200 ... +1200 °C
NoteAccording to DIN EN 60584:
Measuring range type T-200 ... +400 °C
Measuring range type K-200 ... +1360 °C
Measuring range type E-200 ... +1000 °C
Measuring range type N-200 ... +1300 °C
Measuring range type S-40 ... +1760 °C
Measuring range type R-40 ... +1760 °C
Measuring range type B+400 ... +1800 °C
NoteAccording to ASTM standard E988:
Measuring range type C0 ... +2320 °C
Minimum measurement span100 K

Voltage inputs

Measuring ranges-18 ... +18 mV
-36 ... +36 mV
-72 ... +72 mV
-144 ... +144 mV

Current output 20 mA

Output range0 ... 20.4 mA
Resolution10 bit
Accuracy20 µA
Maximum load500 Ohm
Ripple20 µA p-p

Voltage output 10 V

Output range0 ... 10.2 V
Resolution10 bit
Accuracy10 mV
Minimum load5 kOhm
Ripple10 mV p-p
NoteWhen current and voltage outputs are used simultaneously, the two circuits must not be connected together.

Relay outputs A..D

Max. switching voltageAC 250 V AC
Max. AC switching current2 A AC
Max. switching voltageDC 50 V DC
Max. DC switching current2 A DC

Display

Graphic LCD42x64 pixels, RGB backlight
Digital display4-digit, configurable
Display functionScaled input signal, input signal, outputs, limits, scaled value as a bar graph, scaling unit

Transfer characteristics

Measurement rate1 measurement/s
Linearity error0.2 % of full scale
Temperature influence+/-100 ppm/K of full scale

Power supply

Supply voltage50 ... 253 V AC
20 ... 253 V DC
Max. power consumption at 24V DC2.6 W
Max. power consumption at 230V AC5 VA

Housing

DimensionsW×H×D 33x110x128 mm
ConstructionDIN rail 35mm, EN 50022
IP ratingIP 20
Connection technologyRemovable screw terminals, 5 mm pitch
Conductor cross-sectionMax. 2.5 mm2
Weight~ 200 g

Ambient conditions

Permissible ambient temperature-10 ... +60 °C
Storage and transport-10 ... 70 °C (avoid condensation)

EMC

Product family standard 1)EN 61326-1
EmissionsEN 55011, CISR11 class B, group 1
Note1) Minor signal deviations may occur during testing.

Electrical safety

Product family standardEN 61010-1

Galvanic isolation, test voltages

Input to outputs2.5 kV, 1min
Input/outputs to auxiliary supply4 kV, 1min
Between outputsNo galvanic isolation
Input to programming interfaceNo galvanic isolation

Other versions.

Models in the same device family. Differences may include inputs and outputs, power supply or housing type.