DA2000KS Differential pressure indicator with pressure switch in protective housing Smallest measuring range 0...100 Pa
Indicator with diaphragm measuring unit for displaying pressure, negative pressure or differential pressure of non-aggressive gases. Indicator supplied with accessories for mounting in front of or behind a control panel or for wall mounting.
The indicators with diaphragm measuring unit are used to display pressure, negative pressure or differential pressure of non-aggressive gases and are supplied with accessories for mounting in front of or behind a control panel or for wall mounting.
The following extensions are available as options:
- Combination with an adjustable pressure switch via common pressure connection pieces
- Indicator with up to two adjustable red or green limit indicators
| Operating mode: |
| Measuring mode |
| Measuring material: |
| Air or non-aggressive gases |
| Transducer: |
| Mechanical diaphragm measuring unit |
| Measuring unit: |
| Pa |
| Smallest measuring span: |
| 0...150Pa (1mbar) |
| Largest measuring span: |
| 0...5000Pa (50mbar) |
| Measuring ranges: |
| 0...100Pa (1mbar), 0...200Pa (2mbar), 0...500Pa (5mbar), 0...1000Pa (10mbar), 0...2000Pa (20mbar), 0...5000Pa (50mbar) |
| Measuring range selection: |
| Preset ex works |
| Characteristic curve: |
| Linear or square root |
| Switching function: |
| Yes |
| Adjustable switching ranges: |
| 20...300Pa, 30...400Pa, 50...500Pa, 200...1000Pa, 500...2500Pa, 1000...5000Pa |
| Tolerance on upper and lower switching point: |
| ±15% |
| Switching capacity: |
| Max. 1.5A / 250Vac |
| Set point adjustment: |
| Potentiometer with scale |
| Limit signal / alarm output: |
| About pressure switch |
Technical data
- Diaphragm measuring unit
- Smallest measuring range 0...100Pa
- Large analog display (270°) - Scale length approx. 250mm
- Protective housing IP66
- Scaling in m³/h possible
- Combination with a pressure switch
- (1,5A / 250Vac) possible