DPC200-AC, measuring range: 0...6000 Pa (Pascal) Output: 0...10 V (Volt), supply voltage: 90...260 VAC (alternating current) / (50 / 60 Hz)
The DPCs are electromechanical differential pressure/volume flow controllers with a diaphragm measuring system and comprehensive evaluation software. They are used to measure and control the smallest differential pressures of non-aggressive gases, especially air.
The DPCs are electromechanical controllers for differential pressure and volume flow that use a diaphragm measuring system and comprehensive evaluation software. They are ideal for measuring and controlling very low differential pressures of non-aggressive gases, especially air.
They are ideal for use in the field of air conditioning technology, e.g. for controlling fans, monitoring room pressure or regulating filters. The devices make it possible to control the air flow or maintain a constant pressure in a closed environment.
In addition to the analog output, there is a further alarm output (open collector, max. 30 V / 30 mA or relay 250 Vac / 10 A) for limit value monitoring or filter monitoring. The device provides a standardized output signal as a volume flow sensor. For pressure or volume flow control, the output signal is used as a manipulated variable for PI control.
| Operating mode: |
| Measuring mode or control mode |
| Measuring material: |
| Air or non-aggressive gases |
| Transducer: |
| Electromechanical diaphragm measuring unit |
| Measuring unit: |
| Pa / inH2O or m3/h or cfm |
| Smallest measuring span: |
| 0...50Pa (0,5mbar) |
| Largest measuring span: |
| 0...6.000Pa (60mbar) |
| Measuring ranges |
| 0...50Pa (0.5mbar), 0...100Pa (1mbar), 0...500Pa (5mbar), 0...1000Pa (10mbar), 0...2000Pa (20mbar), 0...4000Pa (40mbar), 0...6000Pa (60mbar) |
| Measuring range selection: |
| Preset ex works |
| Adjustable parameters: |
| P/I parameters, k-factor, maximum output voltage, normal / inverse control |
| Characteristic curve: |
| Linear for pressure measurement, root-extracted for volume flow measurement |
| Ambient temperature: |
| -10...+50°C |
| Storage temperature: |
| -25...+60°C |
| Control characteristic: |
| PI - Algorithm |
| Setpoint adjustment: |
| Two setpoints can be set via buttons, selection of setpoints via potential-free contact |
| Limit signal / alarm output: |
| Open collector, max. 30V / 30mA |
| Time delay (Alarm delay time): |
| 12 seconds |
Technical data
- Electromechanical diaphragm measuring system
- Measuring range from 0...50 Pa (0.5 mbar) to 0...6000 Pa (60 mbar)
- Alphanumeric LCD display
- Analog output 0...10 V
- Selectable measurements (differential pressure or volume flow)
- Selectable units (metric or Anglo-American)
- Adjustable k-factor for volume flow calculation
- Measuring mode with adjustable limit value
- Control mode with adjustable:
2 setpoints
PI parameter for PI algorithm
maximum output voltage - Supply voltage 90....260 Vac (50 / 60 Hz)
- Compact plastic housing IP 54