DPC200-MODmeasuring range: 0...6000 Pa (Pascal) Output: 0...10 V (Volt) Supply voltage: 15...30 VDC (direct current), 24 VAC (alternating current)

The DPC200-MOD was developed to combine the functions required in the HVAC sector in one device. Output: 0...10 V, supply voltage: 15...30 Vdc, 24 Vac, for air or non-aggressive gases

Can be ordered in the following variants:

0...50 Pa, 0...100 Pa, 0....200 Pa, 0....400 Pa, 0....500 Pa, 0....1000 Pa, 0....2000 Pa, 0....4000 Pa, 0....5000 Pa, 0....6000 Pa

  • Electromechanical diaphragm measuring system
  • Configuration via Modbus communication
  • Selectable measurements (differential pressure or volume flow)
  • Selectable units (Pa / InH20 or m3/h or cfm)
  • Selectable control mode or measuring mode
  • Control mode with adjustable: setpoint, maximum output voltage,
  • P and I parameterized for PI algorithm, direct or inverse sense
  • Adjustable k-factor for volume flow calculation
  • Analog output 0...10 V
  • Alphanumeric LCD display
  • Supply voltage 22...26 Vdc; 24 Vac (+/-10%)
  • Compact plastic housing IP 54

 

Grubatec-DPC differential pressure controllers / volume flow controllers are suitable for measuring and controlling small differential pressures of non-aggressive gases, especially air. A signal of 0...10V is available to the user as an analog output, the meaning of which varies depending on the setting of the device. When used as a pressure sensor, the output signal is proportional to the measured pressure, while the device provides a square root output signal when used as a volume flow sensor. When used as a pressure or volumetric flow controller, the output signal serves as a manipulated variable for PI control.

The additional Modbus RTU interface is intended for the digitalization of industrial processes. All device parameters can be read and written with the Modbus RTU interface.

A 0...10 V signal output is available for direct analog processing. This signal can be configured as a linear / square root measurement signal or as a manipulated variable of the closed control loop.

It can be used, for example, in air conditioning technology to control fans, monitor room pressure or control filters.

 

 

Measuring material:
Air or non-aggressive gases
Transducer:
Electromechanical diaphragm measuring unit
Measuring unit:
Pa / inH2O or m3/h or cfm
Smallest measuring span:
0...50Pa (0,5mbar)
Largest measuring span:
0...6.000Pa (60mbar)
Measuring range selection:
Four preset measuring ranges, adjustable via software
Adjustable parameters:
P/I parameters, k-factor, maximum output voltage, normal / inverse control
Characteristic curve:
linear or root-extracted
Ambient temperature:
-10...+50°C
Storage temperature:
-25...+60°C
Control characteristic:
PI - Algorithm
Setpoint adjustment:
Two setpoints can be set via buttons, selection of setpoints via potential-free contact
Signal input:
0...10V, multifunctional input (external setpoint: 0...10V input refers to the measuring range; temp. compensated setpoint: 0...10V input refers to -30...+70°C)
Limit signal / alarm output:
Open collector, max. 30V / 30mA
Alarm delay:
Freely adjustable in the range from 0...60 seconds - 2...15 minutes
Freely adjustable in the range from 0...60 seconds - 2...15 minutes

Technical data