DPC200R Measuring range: 0...6000 Pa (Pascal) Output: 0...10 V (Volt)Supply voltage: 15...30 VDC (direct current), 24 VAC (alternating current)

The DPCs are electromechanical differential pressure/volume flow controllers with a diaphragm measuring system and comprehensive evaluation software. They are used to measure and control the smallest differential pressures of non-aggressive gases, especially air.

Can be ordered in the following variants:

0...50 Pa, 0...100 Pa, 0....200 Pa, 0....400 Pa, 0....500 Pa, 0....1000 Pa, 0....2000 Pa, 0....4000 Pa, 0....5000 Pa, 0....6000 Pa

  • electromechanical diaphragm measuring unit
  • Measuring ranges from 0...50 Pa (0.5 mbar) to 0...6000 Pa (60 mbar)
  • alphanumeric LCD
  • Analog output 0...10 V
  • Relay alarm output for measuring and control mode
  • Switchable measured variables (differential pressure or volume flow)
  • Switchable units (metric or Anglo-American)
  • Adjustable k-factor for volume flow calculation
  • Control mode or measuring mode selectable
  • Measuring mode with adjustable limit value
  • Control mode with adjustable:
    • 2 Setpoints
    • PI parameters for PI algorithm
    • Maximum output voltage
    • Control action positive / heating or negative / cooling

 

The DPCs are electromechanical differential pressure controllers with relay function, which can also be used as volume flow controllers with relay output. They are characterized by their mechanical diaphragm measuring mechanism and extensive evaluation electronics and are used to measure and control the smallest differential pressures of non-aggressive gases, especially air.

They are ideal for use in air conditioning technology for controlling fans (HVAC), room pressure monitoring or filter control. The devices can be used to control air flows or constant pressure in a closed environment.

In addition to the analog output, an additional alarm output (relay 250Vac / 10A) is available for limit value monitoring or filter monitoring. As a volume flow sensor, the device provides a square root output signal. For pressure or volume flow control, the output signal is used as a manipulated variable for PI control.

 

Operating mode:
Measuring mode or control mode
Measuring material:
Air or non-aggressive gases
Transducer:
Electromechanical diaphragm measuring unit
Measuring unit:
Pa / inH2O or m3/h or cfm
Smallest measuring span:
0...50Pa (0,5mbar)
Largest measuring span:
0...6.000Pa (60mbar)
Measuring ranges:
0...50Pa (0.5mbar), 0...100Pa (1mbar), 0...500Pa (5mbar), 0...1000Pa (10mbar), 0...2000Pa (20mbar), 0...4000Pa (40mbar), 0...6000Pa (60mbar)
Measuring range selection:
Preset ex works
Adjustable parameters:
P/I parameters, k-factor, maximum output voltage, normal / inverse control
Characteristic curve:
Linear for pressure measurement, square root for volumetric flow measurement
Ambient temperature:
-10...+50°C
Storage temperature:
-25...+60°C
Control characteristic:
PI - Algorithm
Setpoint adjustment:
Two setpoints can be set via buttons, selection of setpoints via potential-free contact
Limit signal / alarm output:
Relay 250Vac / 10A
Time delay (Alarm delay time):
Freely adjustable in the range from 0...60 seconds - 2...15 minutes

Technical data

  • Switchable operating modes
  • (measurement or control)
  • Switchable measured variables
  • (differential pressure or volume flow)
  • Switchable measuring units
  • (Pa andm3/h or inH2Oand cfm)
  • Four preset measuring ranges
  • Analog output 0... 10V
  • Relay alarm output for measuring and control mode
  • Adjustable k-factor for volume flow calculation
  • Measuring mode with adjustable limit value
  • Control mode with adjustable setpoint

 

Request