DPC310 Measuring range: 0...6000 Pa (Pascal) Output 0...10 V (Volt) Three-wire technology, 3 models selectable
The DPC310 is based on the DPC200, but extends its range of functions and is therefore more dynamic than the DPC200. Switchable operating modes (measurement or control) Switchable measured variables (differential pressure or volume flow) Switchable measuring units (Pa and m3 / h or InH2O and cfm) 4 preset measuring ranges Analog output 0 ... 10 V Adjustable k-factor for volume flow calculation Measuring mode with adjustable limit value Control mode with adjustable setpoint: 2 setpoints can be set in the device
Can be ordered in the following variants:
Differential pressure / volume flow controller DPC310-200:
- Measuring range 1: 0 ... 200 Pa or 0 ... 0.8 InH2O
- Measuring range 2: 0 ... 150 Pa or 0 ... 0.6 InH2O
- Measuring range 3: 0 ... 100 Pa or 0 ... 0.4 InH2O
- Measuring range 4: 0 ... 50 Pa or 0 ... 0.2 InH2O
Differential pressure controller DPC310-1000:
- Measuring range 1: 0 ... 1000 Pa or 0 ... 4.0 InH2O
- Measuring range 2: 0 ... 750 Pa or 0 ... 3.0 InH2O
- Measuring range 3: 0 ... 500 Pa or 0 ... 2.0 InH2O
- Measuring range 4: 0 ... 250 Pa or 0 ... 1.0 InH2O
Differential pressure controller DPC310-6000:
- Measuring range 1: 0 ... 6000 Pa or 0 ... 24.0 InH2O
- Measuring range 2: 0 ... 4000 Pa or 0 ... 16.0 InH2O
- Measuring range 3: 0 ... 3000 Pa or 0 ... 12.0 InH2O
- Measuring range 4: 0 ... 2000 Pa or 0 ... 08.0 InH2O
Technical specifications:
- Switchable operating modes (measurement or control)
- Switchable measured variables (differential pressure or volume flow)
- Switchable measuring units (Pa and m3 / h or InH2O and cfm)
- 4 application-oriented preset measuring ranges
- Analog output 0 ... 10 V
- Adjustable k-factor for volume flow calculation
- Measuring mode with adjustable limit
- Control mode with adjustable:
- 2 Setpoints
- Setpoint configurable via external signal input:
- 10 V direct current signal or temperature sensor
- PI parameters for PI algorithm
- Maximum output voltage
- Control effect positive / heat or negative / cool
Grubatec-DPC differential pressure controllers / volume flow controllers are suitable for measuring and controlling small differential pressures of non-aggressive gases, especially air. A signal of 0...10V is available to the user as an analog output, the meaning of which varies depending on the setting of the device. When used as a pressure sensor, the output signal is proportional to the measured pressure, while the device provides a square root output signal when used as a volume flow sensor. When used as a pressure or volumetric flow controller, the output signal serves as a manipulated variable for PI control.
The DPC310 differential pressure controller / volume flow controller is primarily used in air conditioning technology to control fans, for room pressure monitoring or filter control. In addition to the analog output, an additional alarm output (open collector) is available for limit value monitoring or filter monitoring.
Compared to the DPC200, the DPC310 offers an extended range of functions and greater dynamics. In control mode, the setpoint can be set dynamically, either by an external input of a 10 V DC signal or in combination with a temperature sensor. This means that, in addition to pressure and flow rate, other factors such as the outside temperature can also be included in the fan control. Another improvement is the four preset measuring ranges, which have been combined to suit the application. This increases the range of applications and simplifies ordering and stock management.
| Measuring material: |
| Air or non-aggressive gases |
| Transducer: |
| Electromechanical diaphragm measuring unit |
| Measuring unit: |
| Pa / inH2O or m3/h or cfm |
| Smallest measuring span: |
| 0...50Pa (0,5mbar) |
| Largest measuring span: |
| 0...6.000Pa (60mbar) |
| Measuring range selection: |
| Four preset measuring ranges, adjustable via software |
| Adjustable parameters: |
| P/I parameters, k-factor, maximum output voltage, normal / inverse control |
| Characteristic curve: |
| linear or root-extracted |
| Ambient temperature: |
| -10...+50°C |
| Storage temperature: |
| -25...+60°C |
| Control characteristic: |
| PI - Algorithm |
| Setpoint adjustment: |
| Two setpoints can be set via buttons, selection of setpoints via potential-free contact |
| Signal input: |
| 0...10V, multifunctional input (external setpoint: 0...10V input refers to the measuring range; temp. compensated setpoint: 0...10V input refers to -30...+70°C) |
| Limit signal / alarm output: |
| Open collector, max. 30V / 30mA |
| Alarm delay: |
| Freely adjustable in the range from 0...60 seconds - 2...15 minutes |
| Freely adjustable in the range from 0...60 seconds - 2...15 minutes |
Technical data




